Siemens Sinumerik 840D sl Diagnostic Manual page 730

Hide thumbs Also See for Sinumerik 840D sl:
Table of Contents

Advertisement

Overview of Alarms
SINAMICS-Alarms
206321
<location>Master/slave: 6-channel multiplexer control not valid
Message
%1
value:
Drive object:
A_INF
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
Values 0, 1, 2, 3, 4 and 5 are valid to control the 6-channel multiplexer via CI: 3577. In this case, an
invalid value was identified. The control remains effective with the previous value.
Fault value (r0949, interpret decimal):
Invalid value to control the multiplexer.
See also: p3577 (Master/slave current distribution factor, multiplexer selection)
Remedy:
- check the interconnection to control the multiplexer (CI: p3577).
- check the signal source signal value of the BICO interconnection.
See also: p3577 (Master/slave current distribution factor, multiplexer selection)
206350
<location>Infeed: Measured line frequency too high
Message
Line frequency: %1
value:
Drive object:
A_INF, S_INF
Reaction:
NONE
Acknowledge:
NONE
Cause:
The actual line frequency f_line is higher than the parameterized alarm threshold (f_line > p0211 *
p0284).
The alarm can be output in two operating states:
1. During the power-on phase of the infeed unit.
Consequence:
Synchronization of the infeed to the line supply is interrupted and is restarted.
2. While the infeed is operational.
Consequence:
The infeed remains in the operating (run) state and alarm A6350 is output. This signifies a critical oper-
ational fault.
Alarm value (r2124, floating point):
Current line frequency determined.
See also: p0284 (Line supply frequency exceeded, alarm threshold)
Remedy:
- check the parameterized line frequency and if required change (p0211).
- check the alarm threshold (p0284).
- check the line supply.
- check the line supply quality.
See also: p0211 (Rated line freq), p0284 (Line supply frequency exceeded, alarm threshold)
206351
<location>Infeed: Measured line frequency too low
Message
Line frequency: %1
value:
Drive object:
A_INF, S_INF
Reaction:
NONE
Acknowledge:
NONE
Cause:
The actual line frequency f_line is lower than the parameterized alarm threshold (f_line < p0211 *
p0285).
The alarm can be output in two operating states:
1. During the power-on phase of the infeed unit.
Consequence:
Synchronization of the infeed to the line supply is interrupted and is restarted.
2. While the infeed is operational.
Consequence:
The infeed remains in the operating (run) state and alarm A06351 is output. This signifies a critical
operational fault.
Alarm value (r2124, floating point):
Current line frequency determined.
See also: p0285 (Line supply frequency undershot, alarm threshold)
2-730
SINUMERIK 840D sl, 840Di sl, SINAMICS, Diagnostics Manual (DAsl), 03/2009
© Siemens AG 2009 All Rights Reserved
03/2009