Overview of Alarms
SINAMICS-Alarms
Cause:
The ON/OFF1 command is not 0, either via binector input p0840 (current CDS) or in control word
p3982 bit 0.
Remedy:
The signal at binector input p0840 (current CDS) as well as p3982 bit 0 must be 0.
207210
<location>Master control PC/AOP inhibited
Message
-
value:
Drive object:
A_INF, B_INF, S_INF, SERVO, TM41, VECTOR
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The transfer of master control is disabled via binector input p3985.
Remedy:
Change the signal via binector input p3985.
207220
<location>Drive: Master control by PLC missing
Message
-
value:
Drive object:
A_INF, B_INF, S_INF, SERVO, VECTOR
Reaction:
A_INFEED: OFF1 (NONE, OFF2)
SERVO: OFF1 (NONE, OFF2, OFF3, STOP1, STOP2)
VECTOR: OFF1 (NONE, OFF2, OFF3, STOP1, STOP2)
Acknowledge:
IMMEDIATELY
Cause:
The "master control by PLC" signal was missing in operation.
- interconnection of the binector input for "master control by PLC" is incorrect (p0854).
- the higher-level control has withdrawn the "master control by PLC" signal.
- data transfer via the fieldbus (master/drive) was interrupted.
Remedy:
- check the interconnection of the binector input for "master control by PLC" (p0854).
- check the "master control by PLC" signal and, if required, switch in.
- check the data transfer via the fieldbus (master/drive).
Note:
If the drive should continue to operate after withdrawing "master control by PLC" then fault response
must be parameterized to NONE or the message type should be parameterized as alarm.
207300
<location>Drive: Line contactor feedback signal missing
Message
-
value:
Drive object:
A_INF, B_INF, S_INF, SERVO, VECTOR
Reaction:
OFF2 (NONE)
Acknowledge:
IMMEDIATELY
Cause:
- the line contactor was not able to be closed within the time in p0861.
- the line contactor was not able to be opened within the time in p0861.
- the line contactor has dropped out in operation.
- the line contactor has closed although the drive converter is powered down.
Remedy:
- check the setting of p0860.
- check the feedback circuit from the line contactor.
- increase the monitoring time in p0861.
See also: p0860 (Line cont. fdbk sig), p0861 (Line contactor monitoring time)
207311
<location>Bypass motor switch
Message
Fault cause: %1 bin
value:
Drive object:
SERVO, VECTOR
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
2-740
SINUMERIK 840D sl, 840Di sl, SINAMICS, Diagnostics Manual (DAsl), 03/2009