Ge Namespace - GE B30 Communications Manual

Universal relay family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
LNName: LEDsIHMI1
data obj. data attribute
Type
InRef57
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRef58
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRef59
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRef60
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRef61
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP

3.5.7 GE namespace

The GE namespace is an extension of the "IEC 61850-7-4:2007A" namespace, and as such includes by reference all data
object names in IEC 61850-7-4 Edition 2.0 2010-03. As these names are defined in the standard, they are not described in
this document. The GE namespace schema file "GEExtensionsV1_0.xsd" is located in the same folder as the UR EnerVista
software installation, for example in C:\Program Files (x86)\GE Power Management\URPC\GESchema\
The name of the GE namespace specified for firmware 7.4x in this document is "GE Multilin UR Namespace:2015A"
In the last column, the logical node number is not included. For example, LPHD refers to LPHD1.
Table 3-223: GE namespace
Data object
CDC
Semantics
name
AaDmd
MV
Phase A demand.
SRC 1 DMD IA, in primary amperes.
AaMaxDmdDt
MV
Phase A Max Demand with Date (time stamp). The ClcMth cannot be used for
MAX, as the time stamp definition of IEC 61850 is different from UR.
SRC 1 DMD IA MAX, in primary amperes with associated date, SRC 1 DMD IA DATE.
AaRMS
MV
Phase A current RMS.
SRC 1 Phase A Current RMS, in primary amperes.
AbDmd
MV
Phase B demand.
SRC 1 DMD IB, in primary amperes.
AbMaxDmdDt
MV
Phase B Max Demand with Date (time stamp). The ClcMth cannot be used for
MAX, as the time stamp definition of IEC 61850 is different from UR.
SRC 1 DMD IB MAX, in primary amperes with associated date, SRC 1 DMD IB DATE.
AbRMS
MV
Phase B current RMS.
SRC 1 Phase B Current RMS, in primary amperes.
AcDmd
MV
Phase C demand.
SRC 1 DMD IC, in primary amperes.
AcMaxDmdDt
MV
Phase C Max Demand with Date (time stamp). The ClcMth cannot be used for
MAX, as the time stamp definition of IEC 61850 is different from UR.
SRC 1 DMD IC MAX, in primary amperes with associated date, SRC 1 DMD IC DATE.
AcRMS
MV
Phase C current RMS.
SRC 1 Phase C Current RMS, in primary amperes.
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Gen
UR element: Front Panel LEDs
FC UR Name
LED 5 OPERAND setting
LED 6 OPERAND setting
LED 7 OPERAND setting
LED 8 OPERAND setting
LED 9 OPERAND setting
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
Instantiated only if the order code
includes graphical front panel
reference to the data attribute to input
source GoCB of input if via GOOSE
Instantiated only if the order code
includes graphical front panel
reference to the data attribute to input
source GoCB of input if via GOOSE
Instantiated only if the order code
includes graphical front panel
reference to the data attribute to input
source GoCB of input if via GOOSE
Instantiated only if the order code
includes graphical front panel
reference to the data attribute to input
source GoCB of input if via GOOSE
Instantiated only if the order code
includes graphical front panel
reference to the data attribute to input
source GoCB of input if via GOOSE
R/W/C
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
Used in logical nodes...
DmdMtrMMTR
DmdMtrMMTR
ACsrcMMXU
DmdMtrMMTR
DmdMtrMMTR
ACsrcMMXU
DmdMtrMMTR
DmdMtrMMTR
ACsrcMMXU
3-209
3