GE B30 Communications Manual page 285

Universal relay family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
LNName: BusDifPDIF#
data obj. data attribute
Type
stVal
BOOLEAN
DifAClc
WYE
phsθ
CMV
phsθ.instCVal
Vector
phsθ.instCVal.mag
FLOAT32
.f
phsθ.instCVal.ang
FLOAT32
.f
phsθ.cVal
Vector
phsθ.cVal.mag.f
FLOAT32
phsθ.cVal.ang.f
FLOAT32
phsθ.units
Unit
phsθ.units.SIUnit ENUMERATED
phsθ.units
ENUMERATED
.multiplier
phsθ.db
INT32U
phsθ.dbAng
INT32U
phsθ.zeroDb
INT32U
angRef
ENUMERATED
RstA
WYE
phsθ
CMV
phsθ.instCVal
Vector
phsθ.instCVal.mag
FLOAT32
.f
phsθ.instCVal.ang
FLOAT32
.f
phsθ.cVal
Vector
phsθ.cVal.mag.f
FLOAT32
phsθ.cVal.ang.f
FLOAT32
phsθ.units
Unit
phsθ.units.SIUnit ENUMERATED
phsθ.units
ENUMERATED
.multiplier
phsθ.db
INT32U
phsθ.dbAng
INT32U
phsθ.zeroDb
INT32U
angRef
ENUMERATED
InRef2τ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.2.14 Capacitor bank phase overvoltage (CPhOv)
This element is instantiated in the following products: C70.
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: Bus Differential element # (ANSI 87B)
FC UR Name
ST
BUS # SAT θ
MX
BUS # DIFF Iθd magnitude, in
primary amps
BUS # DIFF
MX
BUS # DIFF Iθd magnitude, in
primary amps, with deadband
BUS # DIFF
CF
CF
BusDifPDIF#.DifAClc.phsθ.db
CF
BusDifPDIF#.DifAClc.phsθ.dbAng
CF
CF
MX
BUS # REST Iθr magnitude, in
primary amps
BUS # REXT
MX
BUS # REST Iθr magnitude, in
primary amps, with deadband
BUS # REST
CF
CF
BusDifPDIF#.DifAClc.phsθ.db
CF
BusDifPDIF#.DifAClc.phsθ.dbAng
CF
CF
BUS ZONE #τ STATUS setting
BUS ZONE # DIFF BLK.
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
Phase differential currents
UR range -180...+180 converted to 0...360 R
UR range -180...+180 converted to 0...360 R
5, the code for amps
0, the code for a multiplier of 1
See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
Phase restraint currents
UR range -180...+180 converted to 0...360 R
UR range -180...+180 converted to 0...360 R
5, the code for amps
0, the code for a multiplier of 1
See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
BUS ZONE #τ STATUS setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
BUS ZONE # DIFF BLK setting for setting
group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
R/W/C
R
R
R
R
R
R
R
R
3
R
R
R/W/C
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R/W/C
R/W/C
R
R
R
R/C
R/C
R
R/C
R/C
3-47

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents