GE B30 Communications Manual page 279

Universal relay family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
LNName: B_BFaiRBRF#
data obj. data attribute
Type
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.2.6 B90 bus differential (B_Dif)
This element is instantiated in the following products: B90.
Table 3-24: B90 bus differential data objects
LNName: B_DifPDIF#
data obj. data attribute
Type
StrBia
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
OpBia
ACT
general
BOOLEAN
OpUnBia
ACT
general
BOOLEAN
DpoBia
SPS
stVal
BOOLEAN
PhDir1
SPS
stVal
BOOLEAN
Sat1
SPS
stVal
BOOLEAN
BDifAClc
CMV
instCVal
Vector
instCVal.mag.f
FLOAT32
instCVal.ang.f
FLOAT32
cVal
Vector
cVal.mag.f
FLOAT32
cVal.ang.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32U
dbAng
INT32U
zeroDb
INT32U
BRstA
CMV
instCVal
Vector
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: B90 BREAKER FAILURE logic element
FC UR Name
BF# AMP LOSET OP C for group
γ.
BF# BLK for group γ.
LDevice inst: Prot
UR element: B90 Bus zone # differential element function
FC UR Name
ST
BUS # BIASED PKP
ST
ST
BUS # OP
ST
BUS # BIASED OP
ST
BUS # UNBIASED OP
ST
BUS # BIASED DPO
ST
BUS # DIR
ST
BUS # SAT
MX
BUS ZONE # DIFF current
magnitude
BUS # DIFF current angle
MX
CF
CF
B_DifPDIF#.BDifAClc.db
CF
B_DifPDIF#.BDifAClc.dbAng
CF
MX
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
reference to the data attribute to input
source GoCB of input if via GOOSE
BF# BLK setting for setting group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
BUS # BIASED PKP operand
1 for Forward, and it is mapped to same
operand BUS # BIASED PKP (since
differential DIR logic condition is part of
differential logic)
BUS # OP operand
BUS # BIASED OP operand
BUS # UNBIASED OP operand
BUS # BIASED DPO operand, which is the
inverse of BUS BIASED PKP
BUS # DIR operand
BUS # SAT operand
BUS ZONE # differential current in
primary amps
UR range -180...+180 converted to 0...360 R
instCVal.mag.f deadbanded
instCVal.ang.i deadbanded
5, the code for primary amperes
0, the code for a multiplier of 1
BUS ZONE # restraint current in primary
amps
R/W/C
R/C
R/C
R
R/C
R/C
3
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/W/C
R/W/C
R
R
R
R
R
R
3-41

Hide quick links:

Advertisement

Table of Contents
loading