CHAPTER 2: MODBUS COMMUNICATION
Products
Address Register name
"
DCD6
PMU 1 IDcode
"
DCD7
PMU 1 STN
"
DCDF
PMU 1 Source
"
DCE0
PMU 1 Class
"
DCE1
PMU 1 Format
"
DCE2
PMU 1 Style
"
DCE3
PMU 1 Rate
"
DCE4
PMU 1 PHS-x (14 items)
"
DCF2
PMU 1 PHS-x Name (14 items)
"
DD62
PMU 1 A-CH-x (16 items)
"
DD72
PMU 1 A-CH-x (16 items)
"
DDF2
PMU 1 D-CH-x (16 items)
"
DE12
PMU 1 D-CH-x Name (16 items)
"
DE92
PMU 1 D-CH-x Normal State (16 items)
"
DEA2
PMU 1 Post Filter
"
DEA3
PMU 1 Reserved (15 items)
C60, N60
DEB2
...Repeated for PMU 2
N60
E0B0
...Repeated for PMU 3
"
E2AE
...Repeated for PMU 4
"
E4AC
...Repeated for PMU 5
"
E6AA
...Repeated for PMU 6
Phasor Measurement Unit Aggregator (Read/Write Setting) (1, 2, or 4 Modules)
C60, D60, F60,
E8A8
PMU Aggregator 1 Name
G60, L30, L90,
N60, T60
"
E8C9
Aggregator 1 IDcode
"
E8CA
Aggregator 1 Protocol
"
E8CB
Aggregator 1 TCP Port
"
E8CC
Aggregator 1 UDP Port
"
E8CD
PMU Aggregator 1 90-5 UDP Port
"
E8CE
PMU Aggregator 1 PDC Network Control
"
E8CF
Aggregator 1 Include PMU1
"
E8D0
Aggregator 1 Include PMU2
"
E8D1
Aggregator 1 Include PMU3
"
E8D2
Aggregator 1 Include PMU4
"
E8D3
Aggregator 1 Include PMU5
"
E8D4
Aggregator 1 Include PMU6
"
E8D5
PMU Aggregator 1 ASDUS
"
E8D6
PMU Aggregator 1 Port
"
E8D7
PMU Aggregator 1 Reserved (3 items)
C60, N60
E8D8
...Repeated for PMU Aggregator 2
N60
E908
...Repeated for PMU Aggregator 3
"
E938
...Repeated for PMU Aggregator 4
UR FAMILY – COMMUNICATIONS GUIDE
Range
Units
Step
1 to 65534
---
1
---
---
---
0 to 5
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
0 to 13
---
1
0 to 14
---
1
---
---
---
0 to 65535
---
1
---
---
---
0 to 4294967295
---
1
---
---
---
0 to 1
---
1
0 to 4
---
1
0 to 1
---
1
---
---
---
1 to 65534
---
1
0 to 2
---
1
0 to 65534
---
1
0 to 65534
---
1
0 to 65534
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
1 to 4
---
1
1 to 3
---
1
0 to 1
---
1
MEMORY MAP
Format
Default
F001
1
F203
"GE-UR-
PMU"
F167
0 (SRC 1)
F549
1 (M-CLASS)
F547
0 (Integer)
F546
0 (Polar)
F544
4 (10/sec)
F543
1 (Va)
F203
"GE-UR-
PMU-PHS 1 "
F600
0
F203
"AnalogCha
nnel 1 "
F300
0
F203
"Dig Channel
1 "
F108
0 (Off)
F540
0 (None)
F001
0
F209
"MSVID 1 "
F001
1
F548
0 (NONE)
F001
4712
F001
4713
F001
102
F102
0 (Disabled)
F126
0 (No)
F126
0 (No)
F126
0 (No)
F126
0 (No)
F126
0 (No)
F126
0 (No)
F001
1
F001
1
F001
0
2-179
2