CHAPTER 3: IEC 61850 COMMUNICATION
Table 3-46: Field ground protection stage 1 objects
LNName: FldGnd1PHIZ1
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
Table 3-47: Field ground protection stage 2 objects
LNName: FldGnd2PHIZ1
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
3.5.2.25 Frequency rate of change (RteHz)
This element is instantiated in the following products: D30, D60, F60, G30, G60, L30, L90, N60, T60.
Table 3-48: Frequency rate of change data objects
LNName: RteHzPFRC#
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
HzChgRte
MV
instMag
AnalogueValue
instMag.f
FLOAT32
Mag
AnalogueValue
mag.f
FLOAT32
units
Unit
units.SIUint
ENUMERATED
units.multiplier
ENUMERATED
db
INT32U
zeroDb
INT32U
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: FIELD GROUND element stage 1 functions
FC UR Name
ST
FIELD GND STG1 PKP
ST
ST
FIELD GND STG1 OP
ST
FIELD GND STG1 DPO
LDevice inst: Prot
UR element: FIELD GROUND element stage 2 functions
FC UR Name
ST
FIELD GND STG2 PKP
ST
ST
FIELD GND STG2 OP
ST
FIELD GND STG2 DPO
LDevice inst: Prot
UR element: Frequency Rate of Change element #
FC UR Name
ST
FREQ RATE # PKP
ST
ST
FREQ RATE # OP
ST
FREQ RATE # DPO
MX
FREQUENCY RATE OF CHANGE #
MX
FREQUENCY RATE OF CHANGE #
on deadband exception
CF
CF
RteHzPFRC#.HzChgRte.db
CF
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
FIELD GND STG1 PKP operand
0, the code for unknown. It is unknown as
the element may be connected/
configured to look forward or backward
FIELD GND STG1 OP operand
FIELD GND STG1 DPO operand
Description
FIELD GND STG2 PKP operand
0, the code for unknown. It is unknown as
the element may be connected/
configured to look forward or backward
FIELD GND STG2 OP operand
FIELD GND STG2 DPO operand
Description
FREQ RATE # PKP operand, which is
indicates Op will operate when delay
expires.
0, the code for unknown.
FREQ RATE # OP operand
FREQ RATE # DPO operand
FREQUENCY RATE OF CHANGE # in Hz/s R
75, the code for Rate of change of
frequency (Hz/s)
0, the code for a multiplier of 1
0
R/W/C
R
R
R
R
R
R
R
3
R/W/C
R
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/W/C
R