GE B30 Communications Manual page 320

Universal relay family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Table 3-81: Overfrequency data objects
LNName: OvHzPTOF#
data obj. data attribute
Str
general
dirGeneral
Op
general
Dpo
stVal
BlkRef1
setSrcRef
3
setSrcCB
3.5.2.50 Permissive overreaching transfer trip (POTT_)
This element is instantiated in the following products: D60, L60, L90.
Table 3-82: POTT data objects
LNName: POTT_PSCH1
data obj. data attribute
Op
general
phsA
phsB
phsC
Tr3p
general
Tx1
stVal
Tx2
stVal
Tx3
stVal
Tx4
stVal
BlkRef1
setSrcRef
setSrcCB
InRef5
setSrcRef
setSrcCB
InRef6
setSrcRef
setSrcCB
InRef1
setSrcRef
setSrcCB
InRef2
setSrcRef
3-82
LDevice inst: Prot
UR element: Overfrequency element #
Type
FC UR Name
ACD
BOOLEAN
ST
OVERFREQ # PKP
ENUMERATED
ST
ACT
BOOLEAN
ST
OVERFREQ # OP
SPS
BOOLEAN
ST
OVERFREQ # DPO
ORG
ObjectReference SP
OVERFREQ # BLOCK.
ObjectReference SP
LDevice inst: Prot
UR element: Permissive Over-reaching Transfer Trip element
Type
FC UR Name
ACT
BOOLEAN
ST
POTT OP
BOOLEAN
ST
POTT TRIP A
BOOLEAN
ST
POTT TRIP B
BOOLEAN
ST
POTT TRIP C
ACT
BOOLEAN
ST
POTT TRIP 3P
SPS
BOOLEAN
ST
POTT TX1
SPS
BOOLEAN
ST
POTT TX2
SPS
BOOLEAN
ST
POTT TX3
SPS
BOOLEAN
ST
POTT TX4
ORG
ObjectReference SP
POTT SCHEME BLOCK
ObjectReference SP
ORG
ObjectReference SP
POTT ECHO COND
ObjectReference SP
ORG
ObjectReference SP
GND DIR O/C FWD
ObjectReference SP
ORG
ObjectReference SP
POTT RX1
ObjectReference SP
ORG
ObjectReference SP
POTT RX2
CHAPTER 3: IEC 61850 COMMUNICATION
Description
OVERFREQ # PKP operand which
indicates Op will operate when delay
expires.
0, the code for unknown.
OVERFREQ # OP operand
OVERFREQ # DPO operand
OVERFREQ # BLOCK setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
POTT OP operand
POTT TRIP 3P operand
POTT TX1 operand
POTT TX2 operand
POTT TX3 operand
POTT TX4 operand
POTT SCHEME BLOCK setting
Reference to the data attribute to input R/C
Source GoCB of input if via GOOSE
POTT ECHO COND setting
Reference to the data attribute to input R/C
Source GoCB of input if via GOOSE
GND DIR O/C FWD setting
Reference to the data attribute to input R/C
Source GoCB of input if via GOOSE
POTT RX1 setting
Reference to the data attribute to input R/C
Source GoCB of input if via GOOSE
POTT RX2 setting
Reference to the data attribute to input R/C
UR FAMILY – COMMUNICATIONS GUIDE
R/W/C
R
R
R
R
R
R
R
R
R/C
R/C
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/C
R
R/C
R
R/C
R
R/C
R

Hide quick links: