CHAPTER 3: IEC 61850 COMMUNICATION
Table 3-20: Auxiliary overvoltage data objects
LNName: AuxOvPTOV#
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.2.4 Auxiliary undervoltage (AuxUv)
This element is instantiated in the following products: C60, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, T60.
Table 3-21: Auxiliary undervoltage data objects
LNName: AuxUvPTUV#
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.2.5 B90 breaker failure (B_BFai)
This element is instantiated in the following products: B90.
Table 3-22: B90 breaker failure current data objects
LNName: B_BFaiPIOC#
data obj. data attribute
Type
Op
ACT
general
BOOLEAN
OpHiSet
ACT
general
BOOLEAN
OpLoSet
ACT
general
BOOLEAN
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: Auxiliary Overvoltage element # functions
FC UR Name
ST
AUX OV# PKP
ST
ST
AUX OV# OP
ST
AUX OV# DPO
AUX OV# BLK for group γ.
LDevice inst: Prot
UR element: Auxiliary Undervoltage element# functions
FC UR Name
ST
AUX UV# PKP
ST
ST
AUX UV# OP
ST
AUX UV# DPO
AUX UV# BLOCK for group γ.
LDevice inst: Prot
UR element: B90 BREAKER FAILURE CURRENT SUPV # function
FC UR Name
ST
BKRSUPV # SUPV OP
ST
BKRSUPV # HISET OP
ST
BKRSUPV # LOSET OP
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
AUX OV# PKP operands (including
individual three phases)
0, the code for unknown. It is unknown as
the element is non-directional
AUX OV# OP operand
AUX OV# DPO operand, which is the
inverse of AUX OV PKP
AUX OV# BLK setting for setting group γ. R
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
AUX UV# PKP operands
0, the code for unknown. It is unknown as
the element is non-directional
AUX UV# OP operand
AUX UV# DPO operand, which is the
inverse of AUX UV PKP
AUX UV# BLOCK setting for setting group
γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
BKRSUPV # SUPV OP operand
BKRSUPV # HISET OP operand
BKRSUPV # LOSET OP operand
R/W/C
R
R
R
R
R
R
R
R/C
3
R/C
R/W/C
R
R
R
R
R
R
R
R
R/C
R/C
R/W/C
R
R
R
R
R
R
3-39