CHAPTER 3: IEC 61850 COMMUNICATION
Table 3-56: Line current differential local terminal current data objects
LNName: LinDf0MMXU1
data obj. data attribute
Type
A
WYE
phsθ
CMV
phsθ.instCVal
Vector
phsθ.instCVal.mag
FLOAT32
.f
phsθ.instCVal.ang
FLOAT32
.f
phsθ.cVal
Vector
phsθ.cVal.mag.f
FLOAT32
phsθ.cVal.ang.f
FLOAT32
phsθ.units
Unit
phsθ.units.SIUnit ENUMERATED
phsθ.units
ENUMERATED
.multiplier
phsθ.db
INT32U
phsθ.dbAng
INT32U
phsθ.zeroDb
INT32U
angRef
ENUMERATED
Table 3-57: Line current differential terminal 1 current data objects
LNName: LinDf1MMXU1
data obj. data attribute
Type
A
WYE
phsθ
CMV
phsθ.instCVal
Vector
phsθ.instCVal.mag
FLOAT32
.f
phsθ.instCVal.ang
FLOAT32
.f
phsθ.cVal
Vector
phsθ.cVal.mag.f
FLOAT32
phsθ.cVal.ang.f
FLOAT32
phsθ.units
Unit
phsθ.units.SIUnit ENUMERATED
phsθ.units
ENUMERATED
.multiplier
phsθ.db
INT32U
phsθ.dbAng
INT32U
phsθ.zeroDb
INT32U
angRef
ENUMERATED
Table 3-58: Line current differential terminal 2 current data objects
LNName: LinDf2MMXU1
data obj. data attribute
Type
A
WYE
phsθ
CMV
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: Line Differential element (ANSI 87L) – local terminal current
function
FC UR Name
MX
LOCAL Iθ magnitude, in primary
amps
LOCAL Iθ an
MX
LOCAL Iθ magnitude, in primary
amps, with deadband
LOCAL Iθ an
CF
CF
LinDf0MMXU1.A.phsθ.db
CF
LinDf0MMXU1.A.phsθ.dbAng
CF
CURRENT CUT-OFF LEVEL setting
multiplied by 100000/46.
CF
LDevice inst: Prot
UR element: Line Differential element (ANSI 87L) – terminal 1 current
function
FC UR Name
MX
TERMINAL 1 Iθ magnitude, in
primary amps
TERMINAL 1
MX
TERMINAL 1 Iθ magnitude, in
primary amps, with deadband
TERMINAL 1
CF
CF
LinDf1MMXU1.A.phsθ.db
CF
LinDf1MMXU1.A.phsθ.dbAng
CF
CURRENT CUT-OFF LEVEL setting
multiplied by 100000/46.
CF
LDevice inst: Prot
UR element: Line Differential element (ANSI 87L) – terminal 2 current
function
FC UR Name
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
Local terminal currents
UR range -180...+180 converted to 0...360 R
UR range -180...+180 converted to 0...360 R
5, the code for amps
0, the code for a multiplier of 1
See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
Description
Terminal 1 currents
UR range -180...+180 converted to 0...360 R
UR range -180...+180 converted to 0...360 R
5, the code for amps
0, the code for a multiplier of 1
See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
Description
Terminal 2 currents
R/W/C
R
R
R
R
R
R
3
R
R
R
R/W/C
R/W/C
R
R
R/W/C
R
R
R
R
R
R
R
R
R
R/W/C
R/W/C
R
R
R/W/C
R
R
3-67