CHAPTER 3: IEC 61850 COMMUNICATION
LNName: GndDisPDIS#
data obj. data attribute
Type
phsB
BOOLEAN
dirPhsB
ENUMERATED
phsC
BOOLEAN
dirPhsC
ENUMERATED
Op
ACT
general
BOOLEAN
phsA
BOOLEAN
phsB
BOOLEAN
phsC
BOOLEAN
NeutSupn
SPS
stVal
BOOLEAN
DpoPhsφ
SPS
stVal
BOOLEAN
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.2.28 Ground instantaneous overcurrent (GndIoc)
This element is instantiated in the following products: B30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60,
T35, T60.
Table 3-52: Ground instantaneous overcurrent data objects
LNName: GndIocPIOC#
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
BlkRefγ1
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.2.29 Ground time overcurrent (GndToc)
This element is instantiated in the following products: B30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60,
T35, T60.
Table 3-53: Ground time overcurrent data objects
LNName: GndTocPTOC#
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: Ground Distance Z# Settings
FC UR Name
ST
GND DIST Z# PKP B
ST
dirGeneral
ST
GND DIST Z# PKP C
ST
dirGeneral
ST
GND DIST Z# OP
ST
GND DIST Z# OP A
ST
GND DIST Z# OP B
ST
GND DIST Z# OP C
ST
GND DIST Z# SUPN IN
ST
GND DIST Z#DPO θ
GND DIST Z# BLK.
LDevice inst: Prot
UR element: Ground Instantaneous Overcurrent element#
FC UR Name
ST
GROUND IOC# PKP
ST
ST
GROUND IOC# OP
ST
GROUND IOC# DPO
GROUND IOC# BLOCK.
LDevice inst: Prot
UR element: Ground Time Overcurrent element#
FC UR Name
ST
GROUND TOC# PKP
ST
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
GND DIST Z# OP operand
GND DIST Z# SUPN IN operand
GND DIST Z# DPO θ operand
GND DIST Z# BLK setting for setting group
γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
GROUND IOC# PKP operand, which is
indicates Op will operate when delay
expires.
0, the code for unknown.
GROUND IOC# OP operand
GROUND IOC# DPO operand
GROUND IOC# BLOCK setting in setting
group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
GROUND TOC# PKP operand, which
indicates Op will operate when delay
expires.
0, the code for unknown.
R/W/C
R
R
R
R
R
R
R
R
R
R
R
3
R
R
R
R/C
R/C
R/W/C
R
R
R
R
R
R
R
R
R/C
R/C
R/W/C
R
R
R
3-61

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents