GE B30 Communications Manual page 457

Universal relay family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
Data object
CDC
Semantics
name
PhDir1
SPS
Indicates Phase Comparison of differential is satisfied per phase, where the last
digit of instance number 1, 2, or 3 refers to phase A, B, and C respectively.
The BUS 1 DIR A/B/C operand.
The STATOR DIFF1 DIR A/B/C operand.
PhsAInd
SPS
An LED.
The LED PHASE A operand.
PhsBInd
SPS
An LED.
The LED PHASE B operand.
PhsCInd
SPS
An LED.
The LED PHASE C operand.
PlOpn
ACT
Open pole detector is operated.
The OPEN POLE OP operand.
PosTotVArh
MV
SRC 1 Total VAr-hour in positive direction
PosTotWh
MV
SRC 1 Total Watt-hour in positive direction
ProcBusFail
SPS
Process bus system status.
The PROCESS BUS FAILURE operand.
ProcBusTrbl
SPS
Process bus trouble.
The PROCESS BUS TROUBLE operand.
ProjectedDif
MV
Phase angle difference between V1 and projected V2 (V2').
SYNCHROCHECK 1 DELTA PHASE', in degrees which is the phase angle difference
between V1 and projected V2.
ProjectedV1
CMV
Projected V2 Voltage phasor.
SYNCHROCHECK 1 V2' voltage phasor, in primary volts.
PtpFail
SPS
Bad PTP Signal.
The PTP FAILURE operand.
Raise
SPS
PID 1 RAISE operand value
RawAnsp
MV
Raw neutral split phase current. Raw INsp in per unit.
RawAPh
WYE
Raw Id in per unit for Phase A, B, and C
RecBlk
SPS
Manually block autoreclose.
The BREAKER 1 BLK RCLS operand.
RecEna
SPS
Manually enable autoreclose.
The BREAKER 1 ENA RCLS operand.
RefWinding
INS
Reference winding. Number of windings used as the reference winding for ratio
compensation.
RelDpo
SPS
This data object indicates that not all criteria are fulfilled, and the switching/
operation action is not released to proceed. Complement of Rel.
The SYNC 1 CLS DPO operand, which becomes Off when all synchrocheck criteria
are fulfilled.
RemCmdAcsOff SPS
Indicates operations of FlexLogic operand ACCESS REM CMND OFF
RemCmdAcsOn SPS
Indicates operations of FlexLogic operand ACCESS REM CMND ON
RemMod
SPS
Capacitor control in remote mode.
The CAP 1 IN REMOTE operand.
RemSetAcsOff
SPS
Indicates operations of FlexLogic operand ACCESS REM SETG OFF
RemSetAcsOn
SPS
Indicates operations of FlexLogic operand ACCESS REM SETG ON
RemUnA
SPS
Indicates remote open pole condition is detected in phase A, B, or C.
The OPEN POLE REM OP phase A/B/C operand.
ReSigma
SPC
Command for the Hi-Z Sigma Value Reset
Restart
SPS
Indicates the motor has restarted.
The MOTOR RESTART operand.
RgDstIP
VSG
Expected value of Destination IP address field in messages subscribed to by
RxGOOSE#. The multicast IP address of subscribed R-GOOSE message.
RgRxMode
ENG
R-RxGOOSE1 Reception Mode setting: 0 = Unicast, 1 = SSM; 2=ASM
RgSrcIP
VSG
Expected value of Source IP address field in messages subscribed to by
RxGOOSE#. The source IP address of subscribed R-GOOSE message.
UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Used in logical nodes...
B_DifPDIF, BusDifPDIF,
SttDifPDIF
LEDsIHMI
LEDsIHMI
LEDsIHMI
OpnPlΘSCBR
EnrMtrMMTR
EnrMtrMMTR
LPHD
LPHD
SynChkRSYN
SynChkRSYN
LPHD
PIDRegFPID
NeAUnPTOC
PhAUnPTOC
Bkr0XCBR
Bkr0XCBR
PctDifPDIF
SynChkRSYN
SecGSAL
SecGSAL
CapCtlGAPC
SecGSAL
SecGSAL
OpnPlΘSCBR
HiZPHIZ
MotThmPTTR
LGOS
LGOS
LGOS
3-219
3