MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
LNName: B_DifPDIF#
data obj. data attribute
instCVal.mag.f
instCVal.ang.f
cVal
cVal.mag.f
cVal.ang.f
units
units.SIUnit
units.multiplier
db
dbAng
zeroDb
3
InRefγ01
setSrcRef
setSrcCB
InRefγ02
setSrcRef
setSrcCB
BlkRefγ
setSrcRef
setSrcCB
InRef9ττ
setSrcRef
setSrcCB
3.5.2.7 B90 end fault protection (B_Efp)
This element is instantiated in the following products: B90.
Table 3-25: B90 end fault protection data objects
LNName: B_EfpPIOC#
data obj. data attribute
Str
general
dirGeneral
Op
general
Dpo
stVal
InRefγ1
setSrcRef
setSrcCB
InRefγ2
3-42
LDevice inst: Prot
UR element: B90 Bus zone # differential element function
Type
FC UR Name
FLOAT32
BUS ZONE # REST current
magnitude
FLOAT32
BUS # REST current angle
Vector
MX
FLOAT32
FLOAT32
Unit
CF
ENUMERATED
ENUMERATED
INT32U
CF
B_DifPDIF#.BRstA.db
INT32U
CF
B_DifPDIF#.BRstA.dbAng
INT32U
CF
ORG
ObjectReference SP
BUS ZONE # DIFF SUPV for
group γ.
ObjectReference SP
ORG
ObjectReference SP
BUS ZONE # DIFF TRIP for group
γ.
ObjectReference SP
ORG
ObjectReference SP
BUS ZONE # DIFF BLK for group
γ.
ObjectReference SP
ORG
ObjectReference SP
BUS ZONE #τ STATUS setting
ObjectReference SP
LDevice inst: Prot
UR element: B90 End fault protection element # function
Type
FC UR Name
ACD
BOOLEAN
ST
EFP # PKP
ENUMERATED
ST
ACT
BOOLEAN
ST
EFP # OP
SPS
BOOLEAN
ST
EFP # DPO
ORG
ObjectReference SP
EFP# BREAKER OPEN for group
γ.
ObjectReference SP
ORG
CHAPTER 3: IEC 61850 COMMUNICATION
Description
UR range -180...+180 converted to 0...360 R
instCVal.mag.f deadbanded
instCVal.ang.i deadbanded
5, the code for primary amperes
0, the code for a multiplier of 1
BUS ZONE # DIFF SUPV setting for setting
group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
BUS ZONE # DIFF TRIP setting for setting
group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
BUS ZONE # DIFF BLK setting for setting
group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
BUS ZONE #τ STATUS setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
EFP # PKP operand
0, the code for unknown. It is unknown as
the element is non-directional
EFP # OP operand
EFP # DPO operand, which is the inverse
of EFP PKP
EFP# BREAKER OPEN setting for setting
group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
EFP# MANUAL CLOSE setting for setting
group γ.
UR FAMILY – COMMUNICATIONS GUIDE
R/W/C
R
R
R
R
R
R
R
R/W/C
R/W/C
R
R
R
R
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R/W/C
R
R
R
R
R
R
R
R
R/C
R/C
R