CHAPTER 3: IEC 61850 COMMUNICATION
LNName: PhsTocPTOC#
data obj. data attribute
Type
BlkRefγβ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.2.62 Phase undervoltage (PhsUv)
This element is instantiated in the following products: B30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60,
T60.
Table 3-107: Phase undervoltage data objects
LNName: PhsUvPTUV#
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
phsA
BOOLEAN
dirPhsA
ENUMERATED
phsB
BOOLEAN
dirPhsB
ENUMERATED
phsC
BOOLEAN
dirPhsC
ENUMERATED
Op
ACT
general
BOOLEAN
phsA
BOOLEAN
phsB
BOOLEAN
phsC
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
DpoPhsβ
SPS
stVal
BOOLEAN
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.2.63 Power swing detection (RPSB_)
This element is instantiated in the following products: D30, D60, G60, L60, L90, N60, T60.
Table 3-108: Power swing detection data objects
LNName: PwrSwgRPSB1
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: Phase Time Overcurrent element #
FC UR Name
PHASE TOC# BLOCK β for group
γ (where β refers to Phase-A, B
or C)
LDevice inst: Prot
UR element: Phase Undervoltage element # functions
FC UR Name
ST
PHASE UV# PKP
ST
ST
PHASE UV# PKP A
ST
ST
PHASE UV# PKP B
ST
ST
PHASE UV# PKP C
ST
ST
PHASE UV# OP
ST
PHASE UV# OP A
ST
PHASE UV# OP B
ST
PHASE UV# OP C
ST
PHASE UV# DPO
ST
PHASE UV# DPO β (where β
refers to Phase-A, B or C)
PHASE UV# BLOCK for group γ. reference to the data attribute to input
LDevice inst: Prot
UR element: Power Swing Detect element
FC UR Name
ST
POWER SWING INCOMING
ST
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
PHASE TOC# BLOCK β setting for setting
group γ." (where β refers to Phase-A, B or
C)
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
PHASE UV# PKP operands (including
individual three phases)
0, the code for unknown. It is unknown as
the element is non-directional
0, the code for unknown. It is unknown as
the element is non-directional
0, the code for unknown. It is unknown as
the element is non-directional
0, the code for unknown. It is unknown as
the element is non-directional
PHASE UV# OP operand (including
individual three phases)
PHASE UV# DPO operand, which is the
inverse of PHASE UV PKP
PHASE UV# DPO β operands" (where β
refers to Phase-A, B or C)
PHASE UV# BLOCK setting for setting
group γ.
source GoCB of input if via GOOSE
Description
POWER SWING INCOMING operand
0
R/W/C
R
R/C
R/C
3
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/C
R/C
R/W/C
R
R
R
3-97