GE B30 Communications Manual page 295

Universal relay family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
Table 3-44: Field current undercurrent data objects
LNName: FldAmpPTUC1
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
3.5.2.24 Field ground protection (FldGnd)
This element is instantiated in the following products: G60.
Table 3-45: Field ground protection data objects
LNName: FldGnd0PHIZ1
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
Fail
SPS
stVal
BOOLEAN
GndRis
MV
instMag
AnalogueValue
instMag.f
FLOAT32
mag
AnalogueValue
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32U
zeroDb
INT32U
GndAmp
MV
instMag
AnalogueValue
instMag.f
FLOAT32
mag
AnalogueValue
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32U
zeroDb
INT32U
Vol
MV
instMag
AnalogueValue
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: FIELD GROUND element under current functions
FC UR Name
ST
FIELD UC PKP
ST
ST
FIELD UC OP
ST
FIELD UC DPO
LDevice inst: Prot
UR element: FIELD GROUND INJ UC element functions
FC UR Name
ST
FIELD GND INJ UC PKP
ST
ST
FIELD GND INJ UC OP
ST
FIELD GND INJ UC DPO
ST
GPM-F FAILURE
MX
FIELD GROUND RESIST
MX
CF
CF
FldGnd0PHIZ1.GndRis.db
CF
MX
FIELD GROUND CURRENT
MX
CF
CF
FldGnd0PHIZ1.GndAmp.db
CF
MX
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
FIELD UC PKP operand
0, the code for unknown. It is unknown as
the element may be connected/
configured to look forward or backward
FIELD UC OP operand
FIELD UC DPO operand
Description
FIELD GND INJ UC PKP operand
0, the code for unknown. It is unknown as
the element may be connected/
configured to look forward or backward
FIELD GND INJ UC OP operand
FIELD GND INJ UC DPO operand
GPM-F FAILURE operand
FIELD GROUND RESIST in ohms
instMag.f deadbanded
30, the code for ohm
0, the code for a multiplier of 1
0
FIELD GROUND CURRENT in amperes
instMag.f deadbanded
5, the code for amperes
0, the code for a multiplier of 1
0
FIELD VOLTAGE in volts
R/W/C
R
R
R
R
R
R
R
3
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R
R
R/W/C
R
R
R