GE B30 Communications Manual page 453

Universal relay family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
Data object
CDC
Semantics
name
FltLoopRis
MV
D30, D60, L60, L90 - The fault loop resistance
FltMulti
SPS
Fault indication - Multi phase fault.
The PHASE SELECT MULTI-P operand.
FltRis
MV
L90 - The fault resistance at the fault point
FltSegment
ENS
L90 - Indicates in which segment of the line the fault occurred: 0 = N/A, 1 = LOCAL,
2 = REMOTE 1, 3 = REMOTE 2
FltSLG
SPS
Fault indication - single line to ground.
The PHASE SELECT SLG operand.
FltVoid
SPS
Fault indication - Fault type not detected.
The PHASE SELECT VOID operand.
FrcTrigger
SPC
Command for the Hi-Z Oscillography Force Trigger
FrstEthFail
SPS
First Ethernet failure.
The FIRST ETHERNET FAIL operand.
Function1
ENG
Function Enable/Disable setting: 0 = Disabled, 1 = Enabled (note that TISSUE 670
suggests something like this named SetMod)
FwdOp
SPS
Fault direction is forward.
The NEG SEQ DIR OC1 FWD operand.
The NTRL DIR OC1 FWD operand.
GoDatSetRef
ORG
Expected value of datSet field in messages subscribed to by RxGOOSE#
The setting RxGOOSE1 DatSet.
GoEnaPort1
ENG
Enable all GOOSE on Ethernet port setting: 0 = Disabled, 1 = Enabled
GoID
VSG
Expected value of goID field in messages subscribed to by RxGOOSE#
The setting RxGOOSE1 ID.
GndAmp
MV
Ground current.
The FIELD GROUND CURRENT in amperes.
GndNeutInd
SPS
An LED.
The LED NEUTRAL/GROUND operand.
GndRis
MV
Ground resistance.
FIELD GROUND RESIST in ohms.
STATOR GND. RESIST in kilo ohms.
GpsFail1
SPS
GPS failed at terminal corresponding to instance number.
The 87L DIFF GPS 1 FAIL operand.
GrAct1
SPS
Setting group corresponding to index is active (not instantiated in C30).
The SETTING GROUP ACT 1 operand.
GrdMasterID
VSS
Grand master ID actual value
Ha3NV
MV
Third harmonic component of neutral voltage.
STATOR GND 3RD HARM VN in volts.
Ha3ZroV
MV
Third harmonic component of zero sequence voltage.
STATOR GND 3RD HARM V0 in volts.
HiZIOC
ACT
Indicates phase instantaneous overcurrent has operated
HiZSt
ENS
Represents the status of Hi-Z fault detection function
HzChgRte
MV
Frequency rate of change measured value.
FREQUENCY RATE OF CHANGE 1 in Hz/s.
HzLedInd
SPS
An LED.
The LED FREQUENCY operand.
HzObAccum
MV
FREQUENCY OOB BAND 1 ACCUMULATION in percentage (%)
IdFail1
SPS
ID check for a peer L30/L90 on the channel has failed.
87L DIFF CH 1 ID FAIL operand, which becomes On when the differential element's
ID check for a peer L30 on channel 1 has failed.
IndFailBeh
ENG
Setting to select the behavior of the RxGOOSE Boolean when the sending device is
offline: 0 = On, 1 = Off, 2 = Latest/On, 3 = Latest/Off
IndPos1
DPS
Generic remote DPS input status values: 0 for intermediate-state, 1 for off, 2 for
on, 3 for bad-state.
RxGOOSE DPS1 actual value.
UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Used in logical nodes...
FltRFLO
PhSelGAPC
FltRFLO
FltRFLO
PhSelGAPC
PhSelGAPC
HiZPHIZ
LPHD
Master/LLN0
NegDocRDIR, NeuDocRDIR
LGOS
Master/LLN0
LGOS
FldGnd0PHIZ
LEDsIHMI
FldGnd0PHIZ, SubHaPHIZ
LinDfPDIF
Master/LLN0
TmClkLTMS
StatrPHIZ
StatrPHIZ
HiZPHIZ
HiZPHIZ
RteHzPFRC
LEDsIHMI
HzBnd$PTUF
LinDfPDIF
GGIO3
GGIO3
3-215
3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents