MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
LNName: VtffGAPC#
data obj. data attribute
stVal
Alm1
stVal
VSigLos
stV al
NeutOpn
stV al
3.5.2.84 Wattmetric ground fault (Watt)
3
This element is instantiated in the following products: D30, D60, F35, F60, L60, L90.
Table 3-134: Wattmetric ground fault data objects
LNName: WattPSDE#
data obj. data attribute
Str
general
dirGeneral
Op
general
Watt
instMag
instMag.f
mag
mag.f
units
units.SIUnit
units.multiplier
db
zeroDb
BlkRefγ
setSrcRef
setSrcCB

3.5.3 Control (Ctrl) logical device

The Ctrl logical device contains logical nodes that model UR control and monitoring functions.
The Ctrl logical device is available when the Advanced IEC 61850 option is purchased with the UR device.
3.5.3.1 Logical node zero (LLN0)
LLN0 is instantiated in all UR family devices implementing the Ctrl logical device.
Table 3-135: LLN0 data objects and attributes
LNName: LLN0
data obj. data attribute
Beh
stVal
3-116
LDevice inst: Prot
UR element: VT FUSE FAILURE # function
Type
FC UR Name
BOOLEAN
ST
SRC# VT FUSE FAIL DPO
SPS
BOOLEAN
ST
SRC# VT FF ALARM
SPS
BOOLEAN
ST
SRC# VT FUSE FAIL VOL LOSS
SPS
BOOLEAN
ST
SRC# VT NEU WIRE OPEN
LDevice inst: Prot
UR element: Wattmetric Ground Fault # settings
Type
FC UR Name
ACD
BOOLEAN
ST
WATTMETRIC GND FLT # PKP
ENUMERATED
ST
ACT
BOOLEAN
ST
WATTMETRIC GND FLT # OP
MV
AnalogueValue
MX
FLOAT32
WATT GND FLT # actual value
AnalogueValue
MX
FLOAT32
instMag.f on deadband
exception
Unit
CF
ENUMERATED
ENUMERATED
INT32U
CF
WattPSDE#.Watt.db
INT32U
CF
ORG
ObjectReference SP
WATTMETRIC GND FLT # BLK.
ObjectReference SP
LDevice inst: Ctrl
UR element: Nameplate information for the logical nodes
Type
FC UR Name
ENS
ENUMERATED
ST
CHAPTER 3: IEC 61850 COMMUNICATION
Description
SRC# VT FF ALARM
SRC# VT FUSE FAIL VOL LOSS operand
SRC# VT NEU WIRE OPEN operand
Description
WATTMETRIC GND FLT # PKP operand
0 (unknown).
WATTMETRIC GND FLT # OP operand
SRC # Three Phase Real Power, in primary
watts
38, the code for primary watts (J/s)
0, the code for a multiplier of 1
3-phase power cut-off level in percent
multiplied by 1000
WATTMETRIC GND FLT # BLK setting for
setting group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
This logical device's behaviour
UR FAMILY – COMMUNICATIONS GUIDE
R/W/C
R
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R
R/W/C
R
R
R/C
R/C
R/W/C
R
R