GE B30 Communications Manual page 353

Universal relay family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
Table 3-131: Voltage differential stage objects
LNName: VDif$PDIF#
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
phsA
BOOLEAN
dirPhsA
ENUMERATED
phsB
BOOLEAN
dirPhsB
ENUMERATED
phsC
BOOLEAN
dirPhsC
ENUMERATED
Op
ACT
general
BOOLEAN
phsA
BOOLEAN
phsB
BOOLEAN
phsC
BOOLEAN
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.2.82 Volts per Hertz (VpHz)
This element is instantiated in the following products: G30, G60, L90, T60.
Table 3-132: Volts per Hertz data objects
LNName: VpHzPVPH#
data obj. data attribute
Type
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.2.83 VT fuse failure (Vtff)
This element is instantiated in the following products: C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60, T60.
Table 3-133: VT fuse failure data objects
LNName: VtffGAPC#
data obj. data attribute
Type
FuFail
SPS
stVal
BOOLEAN
Dpo
SPS
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: Voltage Differential element # stage $
FC UR Name
ST
Logical OR of data attributes
phsA, phsB and phsC
ST
ST
VOLT DIF # STG$A PKP
ST
ST
VOLT DIF # STG$B PKP
ST
ST
VOLT DIF # STG$C PKP
ST
ST
Logical OR of data attributes
phsA, phsB, phsC
ST
VOLT DIF # STG$A OP
ST
VOLT DIF # STG$B OP
ST
VOLT DIF # STG$C OP
VOLT DIF # BLK STG$ for group
γ.
LDevice inst: Prot
UR element: Volts per Hertz element #
FC UR Name
ST
VOLTS PER HERTZ # OP
ST
VOLTS PER HERTZ # DPO
ST
VOLTS PER HERTZ # PKP operand
ST
VOLTS/HZ # BLOCK for group γ Reference to the data attribute to input R/C
LDevice inst: Prot
UR element: VT FUSE FAILURE # function
FC UR Name
ST
SRC# VT FUSE FAIL OP
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
VOLT DIF # STG$ PKP operands (including
individual three phases)
0, the code for unknown
0, the code for unknown
0, the code for unknown
0, the code for unknown
VOLT DIF # STG$ OP operands
VOLT DIF # BLK STG$ setting for setting
group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
VOLTS PER HERTZ # OP operand
VOLTS PER HERTZ # DPO operand
VOLTS PER HERTZ # PKP operand
0
VOLTS /HZ # BLOCK setting for setting
group γ
Source GoCB of input if via GOOSE
Description
SRC# VT FUSE FAIL OP operands
SRC# VT FUSE FAIL DPO operand,
R/W/C
R
R
R
R
R
R
R
R
R
3
R
R
R
R
R
R
R/C
R/C
R/W/C
R
R
R
R
R
R
R
R
R/C
R/W/C
R
R
R