CHAPTER 3: IEC 61850 COMMUNICATION
3.5.2.79 Underfrequency (UnHz)
This element is instantiated in the following products: D30, D60, F35, F60, G30, G60, L30, L90, M60, N60, T35, T60.
Table 3-128: Underfrequency data objects
LNName: UnHzPTUF#
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
BlkRef1
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.2.80 Underpower (UnPwr)
This element is instantiated in the following products: M60.
Table 3-129: Underpower data objects
LNName: UnPwrPDUP#
data obj. data attribute
Type
StrAlm
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
OpAlm
ACT
general
BOOLEAN
Op
ACT
general
BOOLEAN
DpoAlm
SPS
stVal
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.2.81 Voltage differential (VDif)
This element is instantiated in the following products: C70.
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: Underfrequency element #
FC UR Name
ST
UNDERFREQ # PKP
ST
ST
UNDERFREQ # OP
ST
UNDERFREQ # DPO
UNDERFREQ # BLOCK.
LDevice inst: Prot
UR element: Under Power element
FC UR Name
ST
UNDERPWR # ALARM PKP
ST
ST
UNDERPWR # TRIP PKP
ST
ST
UNDERPWR # ALARM OP
ST
UNDERPWR # TRIP OP
ST
UNDERPWR # ALARM DPO
ST
UNDERPWR # TRIP DPO
UNDERPOWER # BLOCK for
group γ.
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
UNDERFREQ # PKP operand, which is
indicates Op will operate when delay
expires.
0, the code for unknown.
UNDERFREQ # OP operand
UNDERFREQ # DPO operand
UNDERFREQ # BLOCK setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
UNDERPWR # ALARM PKP operand
0, the code for unknown. It is unknown as
the element is non-directional
UNDERPWR # TRIP PKP operand
0, the code for unknown. It is unknown as
the element is non-directional
UNDERPWR # ALARM OP operand
UNDERPWR # TRIP OP operand
UNDERPWR # ALARM DPO operand
UNDERPWR # TRIP DPO operand
UNDERPOWER # BLOCK setting for
setting group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
R/W/C
R
R
R
R
R
R
3
R
R
R/C
R/C
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/C
R/C
3-113