GE B30 Communications Manual page 441

Universal relay family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
Table 3-216: Security data objects
LNName: SecGSAL1
data obj. data attribute
Type
AuthFail
SEC
cnt
INT32U
sev
ENUMERATED
AcsCtlFail
SEC
cnt
INT32U
sev
ENUMERATED
SvcViol
SEC
cnt
INT32U
sev
ENUMERATED
Ina
SEC
cnt
INT32U
sev
ENUMERATED
SecDataClr
SPC
pulseConfig
PulseConfig
pulseConfig
ENUMERATED
.cmdQual
pulseConfig.onDur INT32U
pulseConfig
INT32U
.offDur
pulseConfig
INT32U
.numPls
ctlModel
CtlModels
sboTimeout
INT32U
sboClass
SboClasses
operTimeout
INT32U
OpCntRs
INC
stVal
INT32
ctlModel
CtlModels
sboTimeout
INT32U
sboClass
SboClasses
operTimeout
INT32U
LocSetAcs
SPS
Off
stVal
BOOLEAN
LocSetAcs
SPS
On
stVal
BOOLEAN
LocCmdAc
SPS
sOn
stVal
BOOLEAN
LocCmdAc
SPS
sOff
stVal
BOOLEAN
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Gen
UR element: UR Basic Security element
FC UR Name
ST
ST
ST
ST
ST
a new counter which increments
by 1, every time the data object
that the client wanted to access
exists, but the requested service
is not allowed
ST
ST
New counter that counts
number of associations
terminated due to inactivity
ST
CF
CF
a new setting
SecGSAL1.SecDataClr.ctlModel
default value 1, range 1...2
CF
CF
CF
ST
Sum of AuthFail + AcsCtlFail +
SvcViol + Ina
CF
a new setting
SecGSAL1.OpCntRs ctlModel
default value 1, range 1...2
CF
CF
CF
ST
ACCESS LOC STG OFF
ST
ACCESS LOC STG ON
ST
ACCESS LOC CMND ON
ST
ACCESS LOC CMND OFF
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
Number of authorisation failures: an
association to the client could not be
established due to an authorisation
failure (fixed at 0)
0
2=major
Counter for Access control failures
detection (fixed at 0)
0
0=Unknown
Counter for Service Violations
3 = Minor
Counter for number of associations
terminated due to inactivity
0=Unknown
Mapped to command Clear Security DataR/Ctrl
0 (pulse)
0 indicated the duration is locally defined R
0
1
1, the code for direct control with normal
security; 2 is code for SBO with normal
security.
30000
0 (operate-once)
0
Data object to clear all 5 security violation
counters
1, the code for direct control with normal
security; 2 is code for SBO with normal
security.
30000
0 (operate-once)
0
ACCESS LOC STG OFF operand
ACCESS LOC STG ON operand
ACCESS LOC CMND ON operand
ACCESS LOC CMND OFF operand
R/W/C
R
R
R
R
R
R
R
R
3
R
R
R
R
R
R
R
R
R/W/C
R
R
R
R/Ctrl
R
R/W/C
R
R
R
R
R
R
R
R
R
R
R
3-203