GE B30 Communications Manual page 349

Universal relay family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
LNName: TrBusPTRC#
data obj. data attribute
Type
dirGeneral
ENUMERATED
InRefαα
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRef99
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
BlkRef1
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.2.77 Trip output (TrOut)
This element is instantiated in the following products: C60, D60, L60, L90.
Table 3-126: Trip output data objects
LNName: TrOutPTRC1
data obj. data attribute
Type
Tr
ACT
general
BOOLEAN
Tr3p
ACT
general
BOOLEAN
Tr1p
ACT
general
BOOLEAN
phsA
BOOLEAN
phsB
BOOLEAN
phsC
BOOLEAN
StrRec3p
SPS
stVal
BOOLEAN
Tr3pFrcd
SPS
stVal
BOOLEAN
StrZ2PhDl
SPS
stVal
BOOLEAN
StrZ2GndDl
SPS
stVal
BOOLEAN
InRef3α
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRef1α
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRef2α
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRef01
ORG
setSrcRef
ObjectReference SP
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: Trip Bus element #
FC UR Name
ST
TRIP BUS # INPUT α setting
TRIP BUS # RESET setting
TRIP BUS # BLOCK.
LDevice inst: Prot
UR element: Trip Output element
FC UR Name
ST
TRIP OUTPUT OP
ST
TRIP 3-POLE
ST
TRIP 1-POLE
ST
TRIP PHASE A
ST
TRIP PHASE B
ST
TRIP PHASE C
ST
TRIP AR INIT 3-POLE
ST
TRIP FORCE 3-POLE
ST
TRIP Z2PH TMR INIT
ST
TRIP Z2GR TMR INIT
TRIP 3-POLE INPUT-α setting
TRIP 1-POLE INPUT-α setting
TRIP RECLOSE INPUT-α setting
START TMR Z2PH Inp1 setting
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
0, the code for unknown
TRIP BUS # INPUT α setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
TRIP BUS # RESET setting, which when On
resets the non-volatile set-dominant
input conditions latch.
reference to the data attribute to input
source GoCB of input if via GOOSE
TRIP BUS # BLOCK setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
TRIP OUTPUT OP (any trip) operand
TRIP 3-POLE operand
general is TRIP 1-POLE operand, phsA is
TRIP PHASE A operand, phsB is TRIP
PHASE B operand and phsC is TRIP PHASE
C operand
TRIP AR INIT 3-POLE operand
TRIP FORCE 3-POLE operand (3-pole trip
mode is being forced)
TRIP Z2PH TMR INIT operand
TRIP Z2GR TMR INIT operand
TRIP 3-POLE INPUT-α setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
TRIP 1-POLE INPUT-α setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
TRIP RECLOSE INPUT-α setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
START TMR Z2PH Inp1 setting.
reference to the data attribute to input
R/W/C
R
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
3
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R
R/C
3-111

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents