MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Data object
CDC
name
InjAmp
MV
InjVol
MV
InService
SPS
IntermSt1
SPS
IntrAlm
SPS
IntrAlmDpo
SPS
3
IrigbFail
SPS
IsoBlk
ACT
IsOn
SPS
IsoPos
ACT
LastClrTm
INS
LastRptTm
INS
LastSqNum
INS
LatchErr
SPS
LeoSt
SPS
LivDea
SPS
LivDeaDpo
SPS
LivLiv
SPS
LivLivDpo
SPS
LivV1
SPS
LoadDev
MV
LocCmdAcsOff
SPS
LocCmdAcsOn
SPS
LocMod
SPS
3-216
Semantics
Injected current.
SH INJECTION AMPS in amperes.
Injected voltage.
INJECTED VOLTAGE in volts.
SH INJECTION VOLTS in volts.
LED indication - Relay In-service. The LED IN SERVICE operand.
Intermediate-status detected.
The BREAKER/SWITCH INTERM operand.
Indicates that the current exceeded the maximum interrupting current rating
during the last interruption event.
The BKR ARC 1 MAX OP operand.
Inverse of IntrAlm.
The BKR ARC 1 MAX DPO operand.
A bad IRIG-B input signal has been detected.
The IRIG-B FAILURE operand.
B90 - Indicates that the isolator position is invalid
Indicates the time of day timer is on.
The TIME OF DAY 1 ON operand.
B90 - Indicates position of isolator. When "On", the related current is included in
differential zone; when "Off", the current is excluded from differential calculations.
Represents the UTC time of user fault reports last cleared time in seconds elapsed
since 1970/01/01, 00.00.00.
The LAST CLEARED DATE actual value.
Represents the UTC time of last user fault report generated time in seconds
elapsed since 1970/01/01, 00.00.00.
The LAST REPORT DATE actual value.
Last sequence number received.
Actual value RxGOOSE1 SqNum.
A difference is detected between the wanted and actual latch contact state.
The LATCHING OUT ERROR operand.
Line end open status.
The LINE PICKUP LEO PKP operand.
This data object indicates that live/dead conditions have been met.
The SYNC 1 DEAD S OP operand, which indicates that live/dead conditions have
been met.
This data object indicates that live/dead conditions have not been met.
The SYNC 1 DEAD S DPO operand, which indicates that live/dead conditions have
not been met.
This data object indicates that both sources are live, and that angle, frequency,
and voltage difference and range conditions have been met.
The SYNC 1 SYNC OP operand, which indicates that both sources are live, and that
angle, frequency, and voltage difference and range conditions have been met.
This data object indicates that one or both sources are not live, or that angle,
frequency, and voltage difference and range conditions have been met.
The SYNC 1 SYNC DPO operand, which indicates that one or both sources are not
live, or that angle, frequency, and voltage difference and range conditions have
been met.
This data object indicates that V1 is above the LivVal1 setting.
The SYNC 1 V1 ABOVE MIN operand, which indicates that V1 is above the LivVal1
setting.
Indicates the motor load standard deviation at the time of the broken rotor bar
data acquisition stage.
LOAD DEV. AT BRB CALC. in x FLA.
Indicates operations of FlexLogic operand ACCESS LOC CMND OFF
Indicates operations of FlexLogic operand ACCESS LOC CMND ON
Capacitor control in local mode.
The CAP 1 IN LOCAL operand.
CHAPTER 3: IEC 61850 COMMUNICATION
Used in logical nodes...
SubHaPHIZ
FldGnd0PHIZ, SubHaPHIZ
LEDsIHMI
BkrΘXCBR, DiscΘXSWI,
GGIO3
CBArc0SCBR
CBArc0SCBR
LPHD
B_IsoSSWI
TmDayGAPC
B_IsoSSWI
UFlt0RFLO
UFlt0RFLO
LGOS
LPHD
LinPkpPIOC
SynChkRSYN
SynChkRSYN
SynChkRSYN
SynChkRSYN
SynChkRSYN
BknRotSVBR
SecGSAL
SecGSAL
CapCtlGAPC