CHAPTER 3: IEC 61850 COMMUNICATION
Table 3-195: AC signal sources data object
LNName: ACsrcMMXN#
data obj. data attribute
Type
Vaux
CMV
instCVal
Vector
instCVal.mag.f
FLOAT32
instCVal.ang.f
FLOAT32
cVal
Vector
cVal.mag.f
FLOAT32
cVal.ang.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32U
dbAng
INT32U
zeroDb
INT32U
angRef
ENUMERATED
VauxRMS
MV
instMag
AnalogueValue
instMag.f
FLOAT32
mag
AnalogueValue
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32U
zeroDb
INT32U
Agnd
CMV
instCVal
Vector
instCVal.mag.f
FLOAT32
instCVal.ang.f
FLOAT32
cVal
Vector
cVal.mag.f
FLOAT32
cVal.ang.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32U
dbAng
INT32U
zeroDb
INT32U
angRef
ENUMERATED
AgndRMS
MV
instMag
AnalogueValue
instMag.f
FLOAT32
mag
AnalogueValue
mag.f
FLOAT32
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Meter
UR element: AC Source #
FC UR Name
MX
SRC # Auxiliary Voltage
Magnitude
SRC # Auxiliary Voltage Angle
MX
CF
CF
MMXN# AuxV.db
CF
MMXN# AuxV.dbAng
CF
CF
MX
SRC # Auxiliary Voltage RMS
MX
CF
CF
MMXN# RMS AuxV DEADBAND
CF
MX
SRC # Ground Current
Magnitude
SRC # Ground Current Angle
MX
CF
CF
MMXN# GndCur.db
CF
MMXN# GndCur.dbAng
CF
CF
MX
SRC # Ground Current RMS
MX
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
SRC # Auxiliary Voltage phasor, in primary
volts
UR range -180...+180 converted to 0...360 R
instCVal.mag.f deadbanded
instCVal.ang.f deadbanded
29, the code for primary volts (W/A)
0, the code for a multiplier of 1
voltage cut-off level.
See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
SRC # Auxiliary Voltage RMS, in primary
volts
instMag.f deadbanded
29, the code for primary volts (W/A)
0, the code for a multiplier of 1
voltage cut-off level.
SRC # Ground Current phasor, in primary
amperes
UR range -180...+180 converted to 0...360 R
instCVal.mag.f deadbanded
instCVal.ang.f deadbanded
5, the code for primary amperes
0, the code for a multiplier of 1
current cut-off level.
See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
SRC # Ground Current RMS, in primary
amperes
instMag.f deadbanded
R/W/C
R
R
R
R
R
R
R
3
R
R
R/W/C
R/W/C
R
R
R
R
R
R
R
R
R
R
R/W/C
R
R
R
R
R
R
R
R
R
R
R/W/C
R/W/C
R
R
R
R
R
R
R
3-183