GE B30 Communications Manual page 316

Universal relay family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
3.5.2.44 Neutral instantaneous overcurrent (NeuIoc)
This element is instantiated in the following products: B30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60,
T60.
Table 3-74: Neutral instantaneous overcurrent data objects
LNName: NeuIocPIOC#
data obj. data attribute
Str
general
dirGeneral
Op
general
3
Dpo
stVal
BlkRefγ1
setSrcRef
setSrcCB
3.5.2.45 Neutral overvoltage (NeuOv)
This element is instantiated in the following products: B30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, T60.
Table 3-75: Neutral overvoltage data objects
LNName: NeuOvPTOV#
data obj. data attribute
Str
general
dirGeneral
Op
general
Dpo
stVal
BlkRefγ
setSrcRef
setSrcCB
3.5.2.46 Neutral time overcurrent (NeuToc)
This element is instantiated in the following products: B30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60,
T60.
Table 3-76: Neutral time overcurrent data objects
LNName: NeuTocPTOC#
data obj. data attribute
Str
general
dirGeneral
Op
3-78
LDevice inst: Prot
UR element: Neutral Instantaneous Overcurrent element #
Type
FC UR Name
ACD
BOOLEAN
ST
NEUTRAL IOC# PKP
ENUMERATED
ST
ACT
BOOLEAN
ST
NEUTRAL IOC# OP
SPS
BOOLEAN
ST
NEUTRAL IOC# DPO
ORG
ObjectReference SP
NEUTRAL IOC# BLOCK.
ObjectReference SP
LDevice inst: Prot
UR element: Neutral Overvoltage element # functions
Type
FC UR Name
ACD
BOOLEAN
ST
NEUTRAL OV# PKP
ENUMERATED
ST
ACT
BOOLEAN
ST
NEUTRAL OV# OP
SPS
BOOLEAN
ST
NETRAL OV# DPO
ORG
ObjectReference SP
NEUTRAL OV# BLK for group γ. reference to the data attribute to input
ObjectReference SP
LDevice inst: Prot
UR element: Neutral Time Overcurrent element #
Type
FC UR Name
ACD
BOOLEAN
ST
NEUTRAL TOC# PKP
ENUMERATED
ST
ACT
CHAPTER 3: IEC 61850 COMMUNICATION
Description
NEUTRAL IOC# PKP operand, which
indicates Op will operate when delay
expires.
0, the code for unknown.
NEUTRAL IOC# OP operand
NEUTRAL IOC# DPO operand
NEUTRAL IOC# BLOCK setting in setting
group γ.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
NEUTRAL OV# PKP operands
0, the code for unknown. It is unknown as
the element is non-directional
NEUTRAL OV# OP operand
NEUTRAL OV# DPO operand, which is the
inverse of NEUTRAL OV PKP
NEUTRAL OV# BLK setting for setting
group γ.
source GoCB of input if via GOOSE
Description
NEUTRAL TOC# PKP operand, which
indicates that Op operates when delay
expires
0, the code for unknown
NEUTRAL TOC# OP operand
UR FAMILY – COMMUNICATIONS GUIDE
R/W/C
R
R
R
R
R
R
R
R
R/C
R/C
R/W/C
R
R
R
R
R
R
R
R
R/C
R/C
R/W/C
R
R
R
R

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents