GE B30 Communications Manual page 369

Universal relay family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
LNName: HzBnd$PTUF1
data obj. data attribute
Type
instMag
AnalogueValue
instMag.f
FLOAT32
mag
AnalogueValue
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32
zeroDb
INT32
3.5.3.16 High-impedance fault detection (HiZ)
This element is instantiated in the following products: F60.
Table 3-153: Hi-Z data objects
LNName: HiZPHIZ1
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
phsA
BOOLEAN
phsB
BOOLEAN
phsC
BOOLEAN
neut
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
DisArmed
SPS
stVal
BOOLEAN
DwnCond
ACT
general
BOOLEAN
phsA
BOOLEAN
phsB
BOOLEAN
phsC
BOOLEAN
neut
BOOLEAN
ArcSuspect
ACT
general
BOOLEAN
phsA
BOOLEAN
phsB
BOOLEAN
phsC
BOOLEAN
neut
BOOLEAN
HiZIOC
ACT
general
BOOLEAN
phsA
BOOLEAN
phsB
BOOLEAN
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Ctrl
UR element: Frequency OOB Accumulator $
FC UR Name
MX
FREQUENCY OOB BAND $
ACCUMULATION
MX
instMag.f deadbanded
exception
CF
CF
HzBnd$PTUF1.HzObAccum.db
CF
LDevice inst: Ctrl
UR element: HI-Z function
FC UR Name
ST
HI-Z ARMED
ST
ST
HI-Z ARC DETECTED
ST
HI-Z ARC DETECTED-A
ST
HI-Z ARC DETECTED-B
ST
HI-Z ARC DETECTED-C
ST
HI-Z ARC DETECTED-N
ST
HI-Z ARC DETECTED DPO
ST
HI-Z DISARMED
ST
HI-Z DOWNED COND
ST
HI-Z DOWNED COND-A
ST
HI-Z DOWNED COND-B
ST
HI-Z DOWNED COND-C
ST
HI-Z DOWNED COND-N
ST
HI-Z ARC SUSPECTED
ST
HI-Z ARC SUSPECTED-A
ST
HI-Z ARC SUSPECTED-B
ST
HI-Z ARC SUSPECTED-C
ST
HI-Z ARC SUSPECTED-N
ST
OR logic of operands (HI-Z IOC A
or HI-Z IOC B or HI-Z IOC C)
ST
HI-Z IOC A
ST
HI-Z IOC B
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
1, the code for dimensionless
-2 is code for percent
0
Description
HI-Z ARMED operand
0, the code for unknown It is unknown as
the element is non-directional.
HI-Z ARC DETECTED operand including
Phases-A, B, C and Neutral
HI-Z ARC DETECTED DPO operand
HI-Z DISARMED operand
HI-Z DOWNED COND operand including
phsA, B, C and Neutral
HI-Z ARC SUSPECTED operand including
Phases-A, B, C and Neutral
HI-Z IOC operand including Phases A, B,
C.
R/W/C
R
R
R
R
R
R
R
R/W/C
R
3
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
3-131

Hide quick links:

Advertisement

Table of Contents
loading