CHAPTER 3: IEC 61850 COMMUNICATION
LNName: StrRtePMRI1
data obj. data attribute
Type
stVal
BOOLEAN
BlkRef
ORG
GEORG
setSrcRef
ObjectReference SP
VISIBLE
STRING255
setSrcCB
ObjectReference SP
VISIBLE
STRING255
cdcNs
VISIBLE
STRING255
cdcName
VISIBLE
STRING255
StrHrLOTm
MV
instMag
AnalogueValue
instMag.f
FLOAT32
mag
Analogue Value MX
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32
zeroDb
INT32
3.5.3.19 PID regulator (PIDReg)
This element is instantiated in the following products: C30, F35.
Table 3-156: PID regulator data objects
LNName: PIDRegFPID#
data obj. data attribute
Type
Raise
SPS
stVal
BOOLEAN
Lower
SPS
stVal
BOOLEAN
Out
MV
instMag
AnalogueValue
instMag.f
FLOAT32
mag
AnalogueValue
mag.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32U
zeroDb
INT32U
DeltaOut
MV
instMag
AnalogueValue
instMag.f
FLOAT32
mag
AnalogueValue
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Ctrl
UR element: Maximum starting rate element
FC UR Name
ST
STARTS-PER-HOUR DPO
STARTS/HR BLK.
SP
Reference to the ultimate source
of value selected by setting
STARTS/HR BLK.
SP
If reference is external to this
IED, mapped to the source's
GOOSE control block, else empty
string
EX
Name of the GE Multilin
namespace at the time of this
firmware release
EX
GEORG
MX
Start/Hour Lockout Time
instMag.f on deadband
exception
CF
CF
StrRtePMRI1.StrHrLOTm.db
CF
LDevice inst: Ctrl
UR element: PID Regulator element #
FC UR Name
ST
PID # RAISE
ST
PID # LOWER
MX
PID # Out
MX
CF
CF
PIDRegFPID#.Out.db
CF
MX
PID # Delta Out
MX
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
STARTS/HR BLK setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
Start/Hour Lockout Time in min
4
0
0
Description
PID # RAISE operand value
PID # LOWER operand value
PID # Out value
instMag.f deadbanded
1, the code for dimensionless
0, the code for a multiplier of 1
0
PID # Delta Out value
R/W/C
R
R
R
R/C
R/C
R/C
R/C
R
3
R
R
R
R
R
R
R
R
R
R/W/C
R
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R/W/C
R
R
R
R
R