CHAPTER 3: IEC 61850 COMMUNICATION
LNName: DCB_PSCH1
data obj. data attribute
Type
setSrcCB
ObjectReference SP
InRef4
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.2.20 Directional comparison blocking (DCB1_)
This element is instantiated in the following products: D60, L90.
Table 3-40: DCB1 data objects
LNName: DCB1_PSCH1
data obj. data attribute
Type
Op
ACT
general
BOOLEAN
phsA
BOOLEAN
phsB
BOOLEAN
phsC
BOOLEAN
Tr3p
ACT
general
BOOLEAN
TxBlk
ACT
general
BOOLEAN
TxStop1
SPS
stVal
BOOLEAN
TxStop2
SPS
stVal
BOOLEAN
TxStop3
SPS
stVal
BOOLEAN
TxStop4
SPS
stVal
BOOLEAN
BlkRef1
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRef06
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRef07
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRef08
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRef09
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRef10
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
InRef11
ORG
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: Directional Comparison Blocking element
FC UR Name
BLOCK SCHEME RX4
LDevice inst: Prot
UR element: Directional Comparison Blocking1 element
FC UR Name
ST
DIR BLOCK1 OP
ST
DIR BLOCK1 TRIP A
ST
DIR BLOCK1 TRIP B
ST
DIR BLOCK1 TRIP C
ST
DIR BLOCK1 TRIP 3P
ST
DIR BLOCK1 TX INIT
ST
DIR BLOCK1 TX1 STOP
ST
DIR BLOCK1 TX2 STOP
ST
DIR BLOCK1 TX3 STOP
ST
DIR BLOCK1 TX4 STOP
BLOCKI1 SCHEME BLOCK.
BLK1 SCHME DIR FWD1
BLK1 SCHME DIR FWD2
BLK1 SCHME DIR FWD3
BLK1 SCHME DIR REV1
BLK1 SCHME DIR REV2
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
source GoCB of input if via GOOSE
BLOCK SCHEME RX4 setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
DIR BLOCK1 OP operand
Instantiated only on products with single
pole tripping.
DIR BLOCK1 TX INIT operand
DIR BLOCK1 TX1 STOP operand
Instantiated only on products with single
pole tripping.
Instantiated only on products with single
pole tripping.
Instantiated only on products with single
pole tripping.
BLOCK1 SCHEME BLOCK setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
BLK1 SCHME DIR FWD1 setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
BLK1 SCHME DIR FWD2 setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
BLK1 SCHME DIR FWD3 setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
BLK1 SCHME DIR REV1 setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
BLK1 SCHME DIR REV2 setting.
reference to the data attribute to input
source GoCB of input if via GOOSE
BLK1 SCHME DIR REV3 setting.
R/W/C
R/C
R
R/C
R/C
3
R/W/C
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R
R/C
R/C
R
3-53

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents