GE B30 Communications Manual page 435

Universal relay family
Hide thumbs Also See for B30:
Table of Contents

Advertisement

CHAPTER 3: IEC 61850 COMMUNICATION
LNName: VCompMMXU1
data obj. data attribute
Type
dbAng
INT32U
zeroDb
INT32U
VolRem2
CMV
instCVal
Vector
instCVal.mag.f
FLOAT32
instCVal.ang.f
FLOAT32
cVal
Vector
cVal.mag.f
FLOAT32
cVal.ang.f
FLOAT32
units
Unit
units.SIUnit
ENUMERATED
units.multiplier
ENUMERATED
db
INT32U
dbAng
INT32U
zeroDb
INT32U
3.5.6.6 Data logger (DatLog)
This element is instantiated in the following products: B30, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,
N60, T35, T60.
Table 3-208: Data logger data objects
LNName: DatLogRDRE1
data obj. data attribute
Type
FltNum
INS
stVal
INT32
RcdMade
SPS
stVal
BOOLEAN
MemClr
SPC
pulseConfig
PulseConfig
pulseConfig
ENUMERATED
.cmdQual
pulseConfig.onDur INT32U
pulseConfig
INT32U
.offDur
pulseConfig
INT32U
.numPls
ctlModel
CtlModels
sboTimeout
INT32U
sboClass
SboClasses
operTimeout
INT32U
InRef1
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Gen
UR element: Current Differential Composite Voltage element
FC UR Name
CF
VCompMMXU1.VolRem1.dbAng
CF
MX
Term 2 Vcomp Mag
Term 2 Vcomp Ang
MX
CF
CF
VCompMMXU1.VolRem2.db
CF
VCompMMXU1.VolRem2.dbAng
CF
LDevice inst: Gen
UR element: Data Logger
FC UR Name
ST
ST
Transitions to true whenever a
new sample is recorded, cleared
to false when recorder is
cleared.
CF
CF
DatLogRDRE1.MemClr.ctlModel
CF
CF
CF
DATA LOGGER TRIGGER setting reference to the data attribute to input
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
0
Term 2 Vcomp phasor, in primary volts
instCVal.mag.f deadbanded
instCVal.ang.f deadbanded
29, the code for primary volts
0, the code for a multiplier of 1
0
Description
Fault number
0 if data logger is cleared, 1 once a
sample has been recorded.
Recording started, timestamp mapped to
NEWEST SAMPLE TIME actual
Clear all data logger records command R/Ctrl
0 (pulse)
2 ms (actually one pass)
0
1
30000
0 (operate-once)
0
DATA LOGGER TRIGGER setting.
source GoCB of input if via GOOSE
R/W/C
R/W/C
R
R
R
R
R
R
R
R
R
R
3
R
R/W/C
R/W/C
R
R/W/C
R
R
R
R
R
R
R
R
R
R/W/C
R
R
R
R
R/C
R/C
3-197

Hide quick links: