MEMORY MAP
Products
Address Register name
IEC 61850 XCBR Configuration (Read/Write Settings) (6 Modules)
All except B90
AB00
"
AB02
"
AB04
2
"
AB06
"
AB09
"
AB12
"
AB1B
"
AB24
"
AB2D
IEC 61850 XCBR Configuration (Read/Write Command) (6 Modules)
All except B90
AB08
IEC 61850 Files (Read Only)
All
AB40
IEC 61850 GGIO4 Analog Input Points Configuration Settings (Read/Write) (32 Modules)
All
AB70
"
AB71
"
AB73
"
AB75
"
AB77
"
AB7E
"
AB85
"
AB8C
"
AB93
"
AB9A
"
ABA1
"
ABA8
"
ABAF
"
ABB6
"
ABBD
"
ABC4
"
ABCB
2-156
FlexLogic Operand for IEC 61850
XCBR.ST.Loc status
FlexLogic Operand for IEC 61850 XCBR
Check Sync Release
FlexLogic Operand for IEC 61850 XCBR
Open Interlock
FlexLogic Operand for IEC 61850 XCBR
Close Interlock
...Repeated for module number 2
...Repeated for module number 3
...Repeated for module number 4
...Repeated for module number 5
...Repeated for module number 6
Command to Clear XCBR OpCnt (Operation
Counter)
IEC 61850 CID Filename
IEC 61850 GGIO4 Analog Input 1 Value
IEC 61850 GGIO4 Analog Input 1 db
(deadband)
IEC 61850 GGIO4 Analog Input 1 Minimum –1000000000000 to
IEC 61850 GGIO4 Analog Input 1 Maximum –1000000000000 to
...Repeated for IEC 61850 GGIO4 Analog
Input 2
...Repeated for IEC 61850 GGIO4 Analog
Input 3
...Repeated for IEC 61850 GGIO4 Analog
Input 4
...Repeated for IEC 61850 GGIO4 Analog
Input 5
...Repeated for IEC 61850 GGIO4 Analog
Input 6
...Repeated for IEC 61850 GGIO4 Analog
Input 7
...Repeated for IEC 61850 GGIO4 Analog
Input 8
...Repeated for IEC 61850 GGIO4 Analog
Input 9
...Repeated for IEC 61850 GGIO4 Analog
Input 10
...Repeated for IEC 61850 GGIO4 Analog
Input 11
...Repeated for IEC 61850 GGIO4 Analog
Input 12
...Repeated for IEC 61850 GGIO4 Analog
Input 13
...Repeated for IEC 61850 GGIO4 Analog
Input 14
CHAPTER 2: MODBUS COMMUNICATION
Range
Units
Step
0 to 4294967295
---
1
0 to 4294967295
---
1
0 to 4294967295
---
1
0 to 4294967295
---
1
0 to 1
---
1
---
---
---
---
---
---
0 to 100000
---
1
---
0.001 F060
1000000000000
---
0.001 F060
1000000000000
UR FAMILY – COMMUNICATIONS GUIDE
Format
Default
F300
0
F300
1
F300
1
F300
1
F126
0 (No)
F209
(none)
F600
0
F003
0
0
1000000