CHAPTER 3: IEC 61850 COMMUNICATION
LNName: B_EfpPIOC#
data obj. data attribute
Type
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.2.8 B90 instantaneous overcurrent (B_Ioc)
This element is instantiated in the following products: B90.
Table 3-26: B90 instantaneous overcurrent data objects
LNName: B_IocPIOC#
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.2.9 B90 time overcurrent (B_Toc)
This element is instantiated in the following products: B90.
Table 3-27: B90 time overcurrent data objects
LNName: B_TocPTOC#
data obj. data attribute
Type
Str
ACD
general
BOOLEAN
dirGeneral
ENUMERATED
Op
ACT
general
BOOLEAN
Dpo
SPS
stVal
BOOLEAN
DpoPhs1
SPS
stVal
BOOLEAN
BlkRefγ
ORG
setSrcRef
ObjectReference SP
setSrcCB
ObjectReference SP
3.5.2.10 B90 undervoltage (B_Uv)
This element is instantiated in the following products: B90.
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Prot
UR element: B90 End fault protection element # function
FC UR Name
EFP# MANUAL CLOSE for group
γ.
EFP# BLOCK for group γ.
LDevice inst: Prot
UR element: B90 Instantaneous Overcurrent element #
FC UR Name
ST
IOC # PKP
ST
ST
IOC # OP
ST
IOC # DPO
IOC# BLOCK
LDevice inst: Prot
UR element: Time Overcurrent element #
FC UR Name
ST
TOC# PKP
ST
ST
TOC# OP
ST
TOC# DPO
ST
TOC# DPO
TOC# BLOCK for group γ
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
reference to the data attribute to input
source GoCB of input if via GOOSE
EFP# BLOCK setting for setting group γ. R
reference to the data attribute to input
source GoCB of input if via GOOSE
Description
IOC # PKP operand, which indicates that
Op operates when delay expires
0, the code for unknown
IOC # OP operand
IOC # DPO operand
IOC# BLOCK setting for setting group γ
Reference to the data attribute to input R/C
Source GoCB of input if via GOOSE
Description
TOC# PKP operand, which indicates that
Op operates when delay expires
0, the code for unknown
TOC# OP operands (including individual
three phases)
TOC# DPO operand
TOC# DPO operand
TOC# BLOCK setting for setting group γ R
Reference to the data attribute to input R/C
Source GoCB of input if via GOOSE
R/W/C
R/C
R/C
R/C
R/C
3
R/W/C
R
R
R
R
R
R
R
R
R/C
R/W/C
R
R
R
R
R
R
R
R
R
R/C
3-43