MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Data object
CDC
name
CompLevel
MV
ConfRev
ING
CrcFail1
SPS
Ctrl
SPS
CurUnb
MV
Day1
SPS
DayofMonth
INS
3
DayofYear
INS
DbMax1
ASG
DbMin1
ASG
Deactivated
SPS
DeaV1
SPS
DeltaOut
MV
DifA2ndH
WYE
DifA5thH
WYE
DifVPh
WYE
DirSupn
SPS
Disabled
SPS
DisArmed
SPS
DischargeTms
MV
Discharging
SPS
DistDet
SPS
3-212
Semantics
Indicates the level of the broken rotor bar spectral component relative to the
spectral component of the system frequency.
The COMPONENT LEVEL in dB.
Expected value of confRev field in messages subscribed to by RxGOOSE#
The CRC error threshold has been exceeded.
The 87L DIFF CH 1 CRCFAIL operand, which becomes On when the differential
element has detected the CRC error threshold has been exceeded on channel 1.
Asserted for one second upon any transition in any mode
% UNBALANCE CURRENT
Current day, where 1 = Sunday. The DAY operand.
Represents the day of current month (range 1 to 31).
The DayOfMonth Actual Value to represent in date of month in number form.
Represents the day of the year (range 1 to 366).
The DayOfYear Actual Value to represent day of year in number form.
Value of "max." in deadband calculations
Value of "min." in deadband calculations
Indicates PUSHBUTTON # OFF state. When user pushbutton is asserted, status is
"false"; when user pushbutton is released, status is "true."
The PUSHBUTTON 1 OFF operand.
This data object indicates that V1 is below the DeaVal1 setting.
The SYNC 1 V1 BELOW MAX operand.
PID Delta Output value
Phase differential current
Phase differential current
Differential voltage in per unit for phase A, B, and C
Directional overcurrent supervision status (not instantiated for zone 1
GndDisPDIS1).
The GND DIST Z2 DIR SUPN operand.
Function is disabled
Indicates the high impedance fault detection element is in disarmed state
Capacitor discharge time in seconds.
CAP 1 DISCHARGE TIME in seconds.
Capacitor bank is discharging.
CAP 1 DISCHARGING operand.
Sensitive current disturbance detector.
For PwrSwgRPSB1, power swing element detected disturbance other than power
swing.
The 50DD SV operand, which becomes On when the 87L disturbance detector has
operated.
The POWER SWING 50DD operand.
CHAPTER 3: IEC 61850 COMMUNICATION
Used in logical nodes...
BknRotSVBR
LGOS
LinDfPDIF
LoVStrGAPC
AmpUnbPTOC
TmDayGAPC
TmDayGAPC
TmDayGAPC
FTDRsGGIO1, GGIO4
FTDRsGGIO1, GGIO4
UsrPbIHMI
SynChkRSYN
PIDRegFPID
PctDifPDIF
PctDifPDIF
VDifPDIF
GndDisPDIS
Rec13pRREC, Rec3pRREC
HiZPHIZ
CapCtlGAPC
CapCtlGAPC
LinDfPDIF, PwrSwgRPSB