SUB-MATRIX
ANALOG INPUT
DEFINITION:
HOW TO MODIFY IT:
POSSIBLE CHOICES:
EXAMPLE:
PARAMETER
LOW ADJUST
HIGH ADJUST
Zero adjust and span adjust are values used to calibrate a temperature loop.
Otherwise choose 0 Value = Factory Calibration
Adjustments are made directly in Engineering unit to the input range.
o
(ex.: 5 = 5
C)
Enter a numeric value.
Up to 3 digits including negative sign and decimal point.
[-99 ... +99]
LOW ADJUST will be added to the 0% of the considered range.
HIGH ADJUST will be added to the 100% of the considered range, so the
calibration is changed.
4-19