WIRING THE RECORDER
2.4.1 Recommendations
All wiring must be in accordance with local electrical codes and should be carried out by
•
authorized experienced personnel.
The ground terminal must be connected before any other wiring (and disconnected
•
last).
A switch in the main supply is recommended near the equipment.
•
If an external fuse is used to protect the electrical circuit to the recorder, the fuse
•
should match the recorder fuse rating (fuse type) as well as for the fuse holder.
Sensor wiring should be run as far as possible from power wiring. (motors, contactors,
•
alarms, etc.)
To reduce stray pick-up, we recommend the use of a twisted pair sensor wiring.
•
EMI effects can be further reduced by the use of shielded cable sensor wiring. The
•
shield must be connected to the ground terminal.
The use of spade terminals on all wiring is recommended.
•