PARAMETER
CURR CALIB
Calibrates the 4 mA and 20 mA references for the selected output.
The "CALIB 4mA" message flashes and the output is supposed to
produce 4 mA. Press the
reaching the 4 mA output.
In the case where you validated via the ENTER key, the " CALIB 20mA"
message flashes and the output is supposed to produce 20 mA.
Calibration starts when pressing the
mA output.
Pressing ENTER makes the calibration stop (the "END CAL" message is
displayed during 3s.)
At any time, SETUP disables the 2 references calibration.
PARAMETER
VIEW CURR
Allows the output current to be displayed under the automatic format.
(from 0 to 24 mA)
Cannot be modified. Press SETUP to escape.
PARAMETER
FORCE CURR
Allows forcing a current output manually on the 0-24 mA range.
Press the
and
keys to modify the output current.
Press SETUP to escape.
[0 ... 24] mA
3 digits after the decimal point
0.000
8-21