SUB-MATRIX
PERIODIC
REPORT
DEFINITION:
HOW TO MODIFY IT:
POSSIBLE CHOICES:
NOTE:
WARNING:
EXAMPLE:
PARAMETER
PERIOD
This parameter corresponds to the computation period of a paragraph relative
to minimum, average and maximum values for each trace and maths result.
Enter a value between 0 and 720 hours with two significant digits after the
decimal point.
0: no periodic report
[0.25 ... 720] in hours and hundredths of hours
The chosen values are automatically corrected to the nearest whole minute to
obtain the computation period.
Default value: 0.00 (00h00)
You can choose parameters from 0.25 hour (15 mn) to 720 hours (30 days) if
you want a periodic report.
If you do not want any periodic report, configure 0 in this parameter or do not
select any trace or maths in the report selection parameter.
You cannot choose parameter numbers between 0.01 and 0.24 hours.
When the recorder prints many messages (ex. CHART DOC, ALARM,
DIGITAL ...), some periodic reports may not be printed.
If the entered value is 0.33, then the computation period is 20 mn.
4. CONFIGURATION
4-98