SUB-MATRIX
ANALOG INPUT
DEFINITION:
HOW TO MODIFY IT:
POSSIBLE VALUES:
SEE ALSO:
NOTE:
PARAMETER
SENSOR
Basic: sensor type used on each channel.
Select a new sensor. Press ENTER. With keys
right sensor type and press ENTER
T/C INT COMP: The sensor is a directly connected thermocouple and the
cold junction compensation of the recorder is used.
T/C EXT COMP: Thermocouple sensor is directly connected to a remote temperature
compensation box *.
* See parameter EXT COMP to configure temperature or analog channels (see page 4-
12) used to measure the external cold junction.
RTD: Sensor is a directly connected RTD or variable resistance device.
TR NL 0-5V: Sensor is a temperature transmitter signal range of 0-5V which is not
linear with temperature.
TR NL 1-5V: Sensor is a temperature transmitter signal range of 1-5V that is not linear
with temperature.
TR NL 0-20mA: Sensor is a temperature transmitter signal range of 0-20mA that is not
linear with temperature.
TR NL 4-20mA: Sensor is a temperature transmitter signal range of 4-20mA that is not
linear with temperature.
LINEAR: Sensor is a transmitter output that is linear with process variable.
SPECIAL: Special sensor connected. Must be specified by special order, or created
using PC application software.
NO ENTRY: No sensor connected or unused input.
RANGE to select the required input range.
Changing the sensor type will automatically change RANGE, LOW
VALUE, HIGH VALUE into predefined values.
Which is dependent on:
1) The type of analog input board installed (linear or universal)
2) If the input type is a directly connected temperature sensor.
The access to all sensors is possible only with an universal input board.
T/C INT COMP and RTD sensors are not accessible with a linear input
board.
4. CONFIGURATION
4-8
CLASSIFICATION
select the