20.10

Setting Behavior at the Time of Transition to RUN

After the data logging settings are registered by the start operation of data logging, set the behavior of data logging when the
following user operations to switch the operating status of the CPU module to RUN are performed (transition to RUN). (
CPU Module Logging Configuration Tool Version 1 Operating Manual (MELSEC iQ-R Series))
• Powering off and on and switching the operating status to RUN
• Resetting and switching the operating status to RUN
• Switching the operating status from STOP to RUN
The logging operation can be set individually for each setting number (1 to 10).
Behavior at the time of a transition to RUN
The behavior can be selected from the following.
■Auto start
The data logging automatically starts after the user operation of starting data logging in CPU Module Logging Configuration
Tool and switching the operating status of the CPU module to RUN.
[Online]  [Logging Status and Operation]
■Start by user operation
The data logging status becomes "Start waiting (no collection)" after the user operation of starting data logging in CPU Module
Logging Configuration Tool and switching the operating status of the CPU module to RUN. To start data logging, operate CPU
Module Logging Configuration Tool to start data logging again.
[Online]  [Logging Status and Operation]
When the auto logging is used, the behavior of the data logging is always "Auto Start", even if the behavior at
transition to RUN is set to "Start by User Operation". ( Page 290 Auto Logging)
Data logging behavior that occurs after operating status of CPU module has changed
Data logging does not continue when the operating state of the CPU module changes from RUN to STOP or PAUSE after it
has been started. The data logging status changes to "RUN waiting (no collection)" and data collection is stopped.