Mitsubishi Electric MELSEC iQ-R Series User Manual page 571

Process cpu module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Error
Error name
Error details and cause
code
2260H
Parameter error
• Network numbers are overlapping.
(network)
2261H
Parameter error
• Different network types (CC IE
(network)
Control extended mode/normal mode)
are set between the control station
and the normal station.
2262H
Parameter error
• When the station number of the
(network)
MELSECNET/H network module is 0,
parameters of PLC to PLC network
are set.
• The station type set in the module
parameters differs from that of the
module actually mounted.
• In the CPU module in redundant
mode, "RJ71GF11-T2" (the model
name cannot be set for the redundant
system) is selected to the model
name in the I/O assignment setting of
the system parameter.
2263H
Parameter error
• Even though the CC-Link IE module
(network)
or MELSECNET/H network module is
mounted, a different CC-Link IE
module or MELSECNET/H network
module is set in the system
parameters ("I/O Assignment
Setting"), or CC-Link IE module or
MELSECNET/H network module
parameters have not been set.
Stop/
Action
continue
Stop
• Check the detailed information
(parameter information) of the
error by executing module
diagnostics using the engineering
tool and correct the parameter
setting corresponding to the
displayed number. If the same
error code is displayed again, the
possible cause is a hardware
failure of the data memory in the
CPU module or the intelligent
function module connected.
Please consult your local
Mitsubishi representative.
Stop
• Check the detailed information
(parameter information) of the
error by executing module
diagnostics using the engineering
tool and correct the parameter
setting corresponding to the
displayed number. If the same
error code is displayed again, the
possible cause is a hardware
failure of the data memory in the
CPU module or the intelligent
function module connected.
Please consult your local
Mitsubishi representative.
Stop
• Correct the station number of the
MELSECNET/H network module.
• Check the detailed information
(parameter information) of the
error by executing module
diagnostics using the engineering
tool and correct the parameter
setting corresponding to the
displayed number.
• In the CPU module in redundant
mode, select "RJ71GF11-
T2(MR)", "RJ71GF11-T2(SR)", or
"RJ71GF11-T2(LR)" (model
names can be set for the
redundant system) to the model
name in the I/O assignment
setting of the system parameter.
If the same error code is displayed
again, the possible cause is a
hardware failure of the data memory
in the CPU module or the intelligent
function module connected. Please
consult your local Mitsubishi
representative.
Stop
• Set the system parameters and
module parameters. If the same
error code is displayed again, the
possible cause is a hardware
failure of the data memory in the
CPU module or the intelligent
function module connected.
Please consult your local
Mitsubishi representative.
Detailed
Diagnostic
information
timing
Parameter
At power-on, at
information
RESET
Parameter
At power-on, at
information
RESET, at
STOP  RUN
state
Parameter
At power-on, at
information
RESET, at
STOP  RUN
state
Parameter
At power-on, at
information
RESET, at
STOP  RUN
state
36 ERROR CODES
569
36.4 List of Error Codes
36

Advertisement

Table of Contents
loading

Table of Contents