No.
Name
SM61
I/O module verification
error
SM62
Annunciator
SM80
Detailed information 1:
Flag in use
SM112
Detailed information 2:
Flag in use
SM150
Power-off/power supply
voltage drop detection
SM151
Power supply module
failure detection
Data stored
Details
Off: Normal
• This relay switches to on when the state of the I/O module
On: Error
is different from one registered during power-on, and the
ON state is maintained even after later recovering to the
normal state.
• I/O module verification is also done for modules on the
remote I/O station.
• In a redundant system with redundant extension base unit,
this relay is set as follows:
Off: Not detected
• This relay switches to on when at least one annunciator is
On: Detected
turned on.
• This relay returns to off when all the annunciators are
turned off.
Off: Not used
This relay switches to on if the detailed information n exists
On: In use
when SM0 switched to on.
Off: Power-on/normal power
• This relay turns on when one or more of the power supply
supply voltage
modules whose power has been shut off or power supply
On: Power-off/voltage drop
voltage has dropped (not including a momentary power
detected/power supply
failure), or one or more of empty slots for the power supply
module not mounted
module are detected on the redundant power supply base
unit or a redundant extension base unit.
• This relay turns on if causes to turn on any bits of SD150
have been occurred.
• This relay turns off if causes to turn on any bits of SD150
have been removed.
• In a multiple CPU system, the flags are stored only to the
CPU No.1.
• In a redundant system with redundant extension base unit,
if power-off or power supply voltage drop is detected in a
power supply module on an extension base unit, the on/off
state is stored only in the CPU module of the control
system, but not stored in the CPU module of the standby
system.
Off: Not detected/power-off/
• This relay turns on when one or more power supply module
no power supply module
failures have been detected on the redundant power supply
On: Detected
base unit or a redundant extension base unit.
• This relay turns on if causes to turn on any bits of SD151
have been occurred.
• This relay turns off if causes to turn on any bits of SD151
have been removed.
• In a multiple CPU system, the flags are stored only to the
CPU No.1.
• In a redundant system with redundant extension base unit,
if a failure of a power supply module on an extension base
unit, the on/off state is stored only in the CPU module of the
control system, but not stored in the CPU module of the
standby system.
If an I/O verification error occurs in a module on an
extension base unit, the on/off state is stored only in the
CPU module of the control system, but not stored in the
CPU module of the standby system.
When the systems are switched, the state before system
switching is held.
When the error is cleared, the CPU module of the
system where the error is cleared clears the value.
Appendix 4 List of Special Relay Areas
Set by (setting
timing)
S (Error)
S (Instruction
execution)
S (Status change)
S (Status change)
A
S (Status change)
APPX