Data Logging Function - Mitsubishi Electric MELSEC iQ-R Series User Manual

Process cpu module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Data logging function

The following is the list of special register areas relating to the data logging function.
No.
Name
SD1210
Data logging setting No.1
Latest storage file number
SD1211
SD1212
Data logging setting No.1
Oldest storage file number
SD1213
SD1214
Data logging setting No.1
Internal buffer free space
SD1215
Data logging setting No.1
Number of processing
overflow occurrences
SD1216
Data logging setting No.1
Data logging error cause
SD1220
Data logging setting No.2
to
SD1226
SD1230
Data logging setting No.3
to
SD1236
SD1240
Data logging setting No.4
to
SD1246
SD1250
Data logging setting No.5
to
SD1256
SD1260
Data logging setting No.6
to
SD1266
SD1270
Data logging setting No.7
to
SD1276
SD1280
Data logging setting No.8
to
SD1286
SD1290
Data logging setting No.9
to
SD1296
SD1300
Data logging setting No.10
to
SD1306
Data stored
Details
Latest storage file
• The latest storage file number
number
• This register is cleared to 0 by the stop command from CPU
Module Logging Configuration Tool.
Oldest storage file
• The oldest storage file number
number
• This register is cleared to 0 by the stop command from CPU
Module Logging Configuration Tool.
Free space size of the
• The amount of free space of the internal buffer is stored in K
internal buffer (K bytes)
bytes. The smaller the value, the higher the generating ratio of
processing overflow.
• For the trigger logging, it refers to the total capacity of internal
buffer until the data for the number of records is collected after a
trigger occurred.
• This register is cleared to 0 by the stop command from CPU
Module Logging Configuration Tool.
Number of processing
• The number of data logging processing overflow occurrences
overflow occurrences
• When overflow occurs, data is lost.
• When the count exceeds 65535, it returns to 0 and starts a new
cycle.
• With "Stop" set for the operation at the time when the number of
save files exceeds the limit, a processing overflow may occur
until the stop operation is completed after the collection of data
corresponding to the specified number of storage files was
completed.
• This register is cleared to 0 when the setting is registered or by
the stop command from CPU Module Logging Configuration
Tool.
Data logging error
Cause of the error generated during data logging operations is
cause
stored.
0: No error
Other than 0: For details on the values stored when an error
occurs, refer to the list of error codes. ( Page 552 List of
Error Codes)
Same configuration as
Data configuration is the same as setting No.1 (SD1210 to
the setting No.1
SD1216).
Same configuration as
Data configuration is the same as setting No.1 (SD1210 to
the setting No.1
SD1216).
Same configuration as
Data configuration is the same as setting No.1 (SD1210 to
the setting No.1
SD1216).
Same configuration as
Data configuration is the same as setting No.1 (SD1210 to
the setting No.1
SD1216).
Same configuration as
Data configuration is the same as setting No.1 (SD1210 to
the setting No.1
SD1216).
Same configuration as
Data configuration is the same as setting No.1 (SD1210 to
the setting No.1
SD1216).
Same configuration as
Data configuration is the same as setting No.1 (SD1210 to
the setting No.1
SD1216).
Same configuration as
Data configuration is the same as setting No.1 (SD1210 to
the setting No.1
SD1216).
Same configuration as
Data configuration is the same as setting No.1 (SD1210 to
the setting No.1
SD1216).
Set by (setting
timing)
S (Status change)
S (Status change)
S (Error)
S (Error)
S (Error)
Same configuration
as the setting No.1
Same configuration
as the setting No.1
Same configuration
as the setting No.1
Same configuration
as the setting No.1
Same configuration
as the setting No.1
Same configuration
as the setting No.1
Same configuration
as the setting No.1
Same configuration
as the setting No.1
Same configuration
as the setting No.1
Appendix 5 List of Special Register Areas
A
APPX
695

Advertisement

Table of Contents
loading

Table of Contents