Behavior in cancellation of forced on/off
Forced on/off registration can be canceled for each input/output device individually.
■Behavior of the device
Inputs/outputs for which forced on/off can be set
Input
Input from the modules mounted on the base unit
Input from LX of CC-Link IE Controller Network or
MELSECNET/H
Input from RX of CC-Link
Input from RX of CC-Link IE Field Network
Input other than above (input without modules actually
mounted)
Output
Output to the modules mounted on the base unit
Output to LY of CC-Link IE Controller Network or
MELSECNET/H
Output to RY of CC-Link
Output to RY of CC-Link IE Field Network
Output other than above (output without modules
actually mounted)
■CPU module operating status
Forced on/off registration can be canceled regardless of the CPU module operating status.
■LED status
The following describes the LED status after forced on/off registration is canceled.
Forced on/off registration status of when the registration is
canceled
Registered on/off information is remaining.
No registered on/off information is remaining.
*1 When other functions that use the FUNCTION LED are being executed, the LED indicator changes its status in accordance with the
status of the functions.
Behavior in batch-cancellation of forced on/off registrations
All the forced on/off registrations can be canceled in a batch.
■Behavior of the device
The behavior of the device is the same as that of cancellation of forced on/off (for each device). ( Page 239 Behavior of
the device)
■CPU module operating status
The behavior of the device is the same as that of cancellation of forced on/off (for each device). ( Page 239 CPU module
operating status)
■LED status
The following describes the LED status after forced on/off registration is canceled in a batch.
Forced on/off registration status of when the registration is
canceled
No registered on/off information is remaining.
*1 When other functions that use the FUNCTION LED are being executed, the LED indicator changes its status in accordance with the
status of the functions.
Change in input/output devices in the program
Changed
The input device is turned on or off in accordance with the on/off state of the modules.
The input device is turned on or off in accordance with the on/off state refreshed from CC-
Link IE Controller Network and MELSECNET/H.
The input device is turned on or off in accordance with the on/off state refreshed from CC-
Link.
The input device is turned on or off in accordance with the on/off state refreshed from CC-
Link IE Field Network.
The input device is turned on or off in
accordance with operation result of the
program.
The operation result of the program is
output.
The output device is turned on or off in
accordance with operation result of the
program. (Refresh to external output is not
executed.)
FUNCTION LED status
Flashing (every 200ms)
*1
Off
FUNCTION LED status
*1
Off
19.1 External Input/Output Forced On/Off Function
Not changed
The input device is turned on or off in
accordance with the registered on/off state.
Data is output in accordance with the
registered on/off state.
The output device is turned on or off in
accordance with the registered on/off state.
(Refresh to external output is not executed.)
19 TEST FUNCTION
19
239