Mitsubishi Electric MELSEC iQ-R Series User Manual page 356

Process cpu module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Executing refresh
Refresh is executed when the CPU module is in RUN and/or STOP (PAUSE) state. For details on the behavior when the CPU
module is in stop error state, refer to CPU module operation upon error detection setting. ( Page 204 CPU module
operation upon error detection setting)
■Behavior during the multiple CPU synchronous interrupt program (I45) execution
If refresh is set to be performed during the multiple CPU synchronous interrupt program (I45) execution, the refresh behavior
when the CPU module is in RUN state varies depending on either of the following conditions. ( Page 363 Multiple CPU
Synchronous Interrupt)
• A program (I45 to IRET) which includes the multiple CPU synchronous interrupt program (I45) exists.
• Event execution type program exists.
The following table lists the refresh behaviors.
: Execute refresh, : Not execute refresh
Execution type
Other than event
The I45 interrupt pointer doesn't exist
execution type
The I45 interrupt pointer exists
Event execution type (I45 interrupt specified)
*1 The PSCAN/PSTOP instruction changes after the next scan, and the POFF instruction changes after the next two scans.
: Execute refresh, : Not execute refresh, : Execution disabled
Execution type
Other than
The I45
event
interrupt pointer
execution
doesn't exist
type
The I45
interrupt pointer
exists
Event execution type (I45
interrupt specified)
*2 Not affect to the behavior.
*3 Operates with the pre-change parameters.
*4 Operates with the post-change parameters.
Configurable data
This section lists the configurable data with the refresh settings.
■Maximum number of settings
Maximum of 32 settings can be configured per CPU module for any refresh setting.
■Data number of points
Data number of points can be configured within the number of points assigned to the area (within the send range of the fixed
scan communication area) in increments of two points. Device duplication between multiple setting numbers is not allowed.
23 MULTIPLE CPU SYSTEM FUNCTION
354
23.4 Data Communication Between CPU Modules
Refresh behavior
STOP state
Refresh behavior triggered by operating status change of the CPU module
RUN
Upon addition
Upon removal of the
state
of the I45
I45 interrupt pointer
interrupt pointer
during online
during online
program change
program change
Refresh behavior after the program
control instruction is executed
RUN state
RUN state
 (stop after changing the execution type
RUN
STOP
After the refresh
to
state
setting is
STOP
changed; when
state
parameters are
written
*3
*2
*3
*2
*3
*1
)
STOP
Power
to
off and
RUN
on/Reset
state
*3
*4
*3
*4

Advertisement