Mitsubishi Electric MELSEC iQ-R Series User Manual page 680

Process cpu module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

No.
Name
SD113 to
Detailed
SD143
information 2
SD150
Power-off/power
supply voltage
drop detection
status
APPX
678
Appendix 5 List of Special Register Areas
Data stored
Detailed information 2
Power-off/power supply voltage
drop detection status (bit
pattern)
0: Power-on/normal voltage
1: Power-off/voltage drop
detected/no power supply
module
Details
(29) Other station error information (CC-Link IE Field)
■SD113: With or without specification
∙∙∙
bF
b7
b6
b5 b4 b3 b2 b1 b0
∙∙∙
b0: Error classification
b1: Error code
b2: Date (yyyymmdd)
b3: Time (hhmmss)
b4: Day of the week
b5: Detailed error information 1
b6: Detailed error information 2
b7 to bF: Detailed error information 3 to detailed error information
10
■SD114: Error classification
■SD115: Error code
■SD116 and SD117: Date (yyyymmdd)
• SD116: Lower word of date (yyyymmdd)
• SD117: Upper word of date (yyyymmdd)
■SD118 and SD119: Time (hhmmss)
• SD118: Lower word of time (hhmmss)
• SD119: Upper word of time (hhmmss)
■SD120: Day of the week
■SD121: Detailed error information 1
■SD122: Detailed error information 2
■SD123 to SD130: Detailed error information 3 to 10
• For the redundant power supply base unit or redundant extension
base unit, the power supply module status (power is shut off,
power supply voltage drop (not including a momentary power
failure) is detected, or an empty slot for the power-supply module
exists) is stored using the following bit pattern.
• In a multiple CPU system, the status is stored only to the CPU
module No.1.
• In a redundant system with redundant extension base unit, if
power-off or power supply voltage drop is detected in a power
supply module on an extension base unit, the state is stored only
in the CPU module of the control system, but not stored in the
CPU module of the standby system.
(2)
b15
b9
b8
b7
(1) Powered-off/power supply voltage dropped (power supply
module 1)
b0: Main base unit
b1 to b7: 1st to 7th level of the extension base unit
(2) Powered-off/power supply voltage dropped (power supply
module 2)
b8: Main base unit
b9 to b15: 1st to 7th level of the extension base unit
Set by
(setting
timing)
S (Error)
S (Status
change)
(1)
b2
b1
b0