Mitsubishi Electric MELSEC iQ-R Series User Manual page 696

Process cpu module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

No.
Name
SD954
CPU module data
backup/restoration
function
Restoration function
SD955
SD956
SD957
SD958
SD959
SD960
CPU module data
backup/restoration
function
Backup function
SD988
Memory copy
completion status
(latch)
*1 There are restrictions on the firmware version of the CPU module and software version of the engineering tool. ( Page 747 Added
and Enhanced Functions)
APPX
694
Appendix 5 List of Special Register Areas
Data stored
Restoration target data
setting
*1
Restoration function
setting
Restoration target date
folder setting
Restoration target
number folder setting
Restoration error cause
Upper limit status for the
number of CPU module
backup data
*1
Memory copy
completion status (latch)
Details
Set the target data to be restored with the CPU module data restoration
function.
0: All the target data
1: Device/label data only
2: All the target data except for the device/label data
Set the CPU module data restoration function using the following bit
pattern. (Off: Disabled, On: Enabled)
b15
b14
b13
b2
b1
0
b0:
Automatic restoration
b1:
Initialization at automatic restoration
b2:
Automatic restoration with SD CARD OFF button
b13: Latest data
b14: Special relay and special register
b15: Continuous operation with the status at backup
Store the target folder (date folder) of the CPU module data restoration
using BCD code.
SD957
SD956
b31
b24 b23
b16
b15
b8 b7
(4)
(3)
(2)
(1) Day (1 to 31)
(2) Month (1 to 12)
(3) Year (last two digits) (0 to 99)
(4) Year (first two digits) (0 to 99)
(Example) To specify the date folder of June 15 2015, store
"H20150615".
Specify the target folder of the CPU module data restoration.
1 to 32767: Serial number of the backup folder (*****) in a date folder
(00001 to 32767)
• The cause of an error that occurred during the CPU module data
restoration is stored.
0H: No error
Other than 0: For details on the values stored when an error occurs,
refer to the list of error codes. ( Page 552 List of Error Codes)
• "0" is set at the start of the CPU module data backup.
This register indicates the set value of the upper limit for the number of
backup data in accordance with bit 5 of SD944.
Bit 5 of SD944 is off: 0
Bit 5 of SD944 is on: 1 to 100
This register stores a value indicating the completion status of the
memory copy from the control system to the standby system.
• The value same as the SD1654 value is stored at the completion or
abend of the memory copy from the control system to the standby
system.
• Since data have been backed up in case of power failure, this register
holds the value indicating the latest memory copy completion status
from the control system to the standby system.
• This register is cleared to 0 by latch clear.
b0
b0
(1)
Set by (setting
timing)
U
U
U
U
U
S (Error)
S (Status change)
S (Status change)

Advertisement

Table of Contents
loading

Table of Contents