System clock
The following is the list of special relay areas relating to the system clock.
No.
Name
SM400
Always On
SM401
Always Off
SM402
After RUN, ON for 1 scan
only
SM403
After RUN, OFF for 1
scan only
SM409
0.01 second clock
SM410
0.1 second clock
SM411
0.2 second clock
SM412
1 second clock
SM413
2 second clock
SM414
2n second clock
SM415
2n millisecond clock
APPX
652
Appendix 4 List of Special Relay Areas
Data stored
ON
OFF
ON
OFF
ON
1 scan
OFF
ON
1 scan
OFF
0.005s
0.005s
0.05s
0.05s
0.1s
0.1s
0.5s
0.5s
1s
1s
n s
n s
n ms
n ms
Details
Always On
Always Off
• This relay is on during only one scan after RUN mode
starts.
• This relay is enabled only for the scan execution type
program.
• This relay is off during only one scan after RUN mode
starts.
• This relay is enabled only for the scan execution type
program.
• This relay repeats on/off at 5ms intervals.
• This relay does not turn on/off per scan, but turns on/off
whenever the specified time interval is reached.
• The initial state when the CPU module is powered on or
reset is off.
• This relay repeats on/off at certain intervals.
• This relay does not turn on/off per scan, but turns on/off
whenever the specified time interval is reached.
• The initial state when the CPU module is powered on or
reset is off.
• This relay repeats on/off at certain intervals.
• This relay does not turn on/off per scan, but turns on/off
whenever the specified time interval is reached.
• The initial state when the CPU module is powered on or
reset is off.
• This relay repeats on/off at certain intervals.
• This relay does not turn on/off per scan, but turns on/off
whenever the specified time interval is reached.
• The initial state when the CPU module is powered on or
reset is off.
• This relay repeats on/off at certain intervals.
• This relay does not turn on/off per scan, but turns on/off
whenever the specified time interval is reached.
• The initial state when the CPU module is powered on or
reset is off.
• This relay repeats on/off at regular intervals specified in
SD414 (in units of seconds). (When the value in SD414
is changed, the elapsed time count that has started
when the ON/OFF state of SM414 last changed
continues, and the ON/OFF state changes when the
*1
new specified time is elapsed.
• This relay does not turn on/off per scan, but turns on/off
whenever the specified time interval is reached.
• The initial state when the CPU module is powered on or
reset is off.
• This relay repeats on/off at regular intervals specified in
units of milliseconds on the SD415. (When the value in
SD415 is changed, the elapsed time count that has
started when the ON/OFF state of SM415 last changed
continues, and the ON/OFF state changes when the
*1
new specified time is elapsed.
• This relay does not turn on/off per scan, but turns on/off
whenever the specified time interval is reached.
• The initial state when the CPU module is powered on or
reset is off.
Set by (setting
timing)
S (Power-on to RUN/
STOP to RUN/every
END)
S (Power-on to RUN/
STOP to RUN/every
END)
S (Status change/every
END)
S (Status change/every
END)
S (Status change)
S (Status change)
S (Status change)
S (Status change)
S (Status change)
S (Status change)
)
S (Status change)
)