Mitsubishi Electric MELSEC iQ-R Series User Manual page 564

Process cpu module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Error
Error name
code
2005H
Module
configuration
error
2006H
Module
configuration
error
2007H
Module
configuration
error
2008H
Module
configuration
error
2009H
Module
configuration
error
2020H
Module
configuration
error
2021H
Module
configuration
error
2022H
Module
configuration
error
36 ERROR CODES
562
36.4 List of Error Codes
Error details and cause
• Two or more interrupt modules (QI60)
with no interrupt pointer setting are
mounted.
• The interrupt pointer numbers are
overlapping in the interrupt module
(QI60) with no interrupt pointer setting
and a module with an interrupt pointer
setting.
• A module is mounted on the 65th slot
or later.
• A module is mounted on the slot
whose number is later than that
specified in the system parameters
("I/O Assignment Setting").
• A module is mounted over or across
the maximum number of I/O points
(4096).
• There is no response from the I/O
module or intelligent function module
accessed.
• There is a mounted module that is not
supported, or there is a mounted
module that is not supported by the
network type (module model name)
set in system parameters ("I/O
Assignment Setting").
• In a multiple CPU system, the control
CPU of the Q series intelligent
function module incompatible with the
multiple CPU system is set to other
than CPU No.1.
• A power supply module other than the
redundant power supply module has
been mounted on the redundant
power supply base unit.
Stop/
Action
continue
Stop
• Mount only one QI60 in the entire
system.
• Configure the interrupt pointer
setting for the QI60.
• Correct the interrupt pointer
setting.
Stop
• Remove the module mounted on
the 65th slot or later.
Stop
• Remove the module mounted on
the slot whose number is later
than that specified in the system
parameters.
Stop
• Remove the module mounted over
or across the maximum number of
I/O points (4096).
• Replace the module mounted on
the last slot with the one that does
not exceed the maximum number
of I/O points (4096).
Stop
• Check and correct the I/O
assignment setting in the system
parameters.
• Take measures to reduce noise.
• Reset the CPU module and run it
again. If the same error code is
displayed again, the possible
cause is a hardware failure of the
I/O module or intelligent function
module. Please consult your local
Mitsubishi representative.
Stop
• Remove the unsupported module
if any.
• Check whether modules are
supported by the network type
(module model name) set in the
system parameters.
• If all the modules are supported,
the possible cause is a hardware
failure of the CPU module, base
unit, I/O module, or intelligent
function module. Please consult
your local Mitsubishi
representative.
Stop
• Replace the Q series intelligent
function module with the one
(function version B) compatible
with the multiple CPU system.
• Set the control CPU of the Q
series intelligent function module
incompatible with the multiple
CPU system to CPU No.1.
Stop
• Mount only the redundant power
supply module. If the same error
code is displayed again, the
possible cause is a hardware
failure of the power supply
module, CPU module, or base
unit. Please consult your local
Mitsubishi representative.
Detailed
Diagnostic
information
timing
System
At power-on, at
configuration
RESET, at
STOP  RUN
information
state
System
At power-on, at
configuration
RESET
information
System
At power-on, at
configuration
RESET
information
System
At power-on, at
configuration
RESET
information
System
Always
configuration
information
System
At power-on, at
configuration
RESET
information
System
At power-on, at
configuration
RESET
information
System
At power-on, at
configuration
RESET
information