20.1

Data Logging Procedure

This section describes the data logging procedure.
1.
Install CPU Module Logging Configuration Tool.
 CPU Module Logging Configuration Tool/GX LogViewer Installation Instructions (BCN-P5999-0506)
2.
Launch CPU Module Logging Configuration Tool.
3.
Configure the data logging setting.
 CPU Module Logging Configuration Tool Version 1 Operating Manual (MELSEC iQ-R Series)
4.
If auto logging is used, configure the common settings (auto logging common settings).
Page 291 Auto logging common setting
5.
Insert an SD memory card to the CPU module, and power on the module.
6.
Connect the CPU module to a personal computer.
7.
Write the data logging setting to the SD memory card or data memory.
8.
Switch the CPU module to RUN state to start the data logging.
9.
Stop the data logging and read the data logging file.
10.
Check the file into which data has been read.
• To start data logging, always click the [Start] button in the "Logging Status and Operation" window of CPU
Module Logging Configuration Tool. The data logging cannot be started even when the setting is written and
power is turned off and on or the CPU module is reset (except for the auto logging).
• For the operation procedures for CPU Module Logging Configuration Tool, refer to the following.
 CPU Module Logging Configuration Tool Version 1 Operating Manual (MELSEC iQ-R Series)
20 DATA LOGGING FUNCTION