If more than 16 annunciators are turned on, the 17th annunciator onwards are not stored into SD64 to SD79.
However, if the numbers of annunciators registered in SD64 to SD79 are turned off, the lowest numbers,
which are not registered in SD62 to SD79, of the numbers of annunciators which were turned on for the 17th
on and after, are stored into SD64 to SD79.
(4)
SET F100
SD62
10
SD63
16
SD64
10
SD65
11
SD79
25
(1)
(1) Annunciators have been stored for the maximum number (16).
(2) Because annunciators have been stored for the maximum number, the value does not change.
(3) The smallest number is stored.
(4) Turn on the 17th device.
(5) Turn on the 18th device.
(6) Turn off the first device.

Link special relay (SB)

The communication status and error detection status of network modules, such as the CC-Link IE Controller Network module,
are output to the link special relay (J\SB) on the network. The link special relay (SB) is a device for using as a refreshing
target of link special relays in the network. The part which is not used for refreshing can be used for other applications.
(1)
Used in a program.
SB65
Program
(1) The network status is checked.
(5)
(6)
SET F50
RST F10
SD62
10
SD62
10
SD62
SD63
16
SD63
16
SD63
SD64
10
SD64
10
SD64
SD65
11
SD65
11
SD65
SD79
SD79
SD79
25
25
(2)
CPU module
SB
SB0065
11
16
11
12
(3)
50
CC-Link
IE Controller Network module
SB
Refresh
SB0065
Set the own
station link status.