Mitsubishi Electric MELSEC iQ-R Series User Manual page 557

Process cpu module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Error
Error name
Error details and cause
code
1166H
TCP/IP send
• Data was not sent correctly with TCP/
failed
IP.
1167H
Unsend data
• Unsent data found, but could not be
send error
sent.
1180H
Redundant IP
• The same IP address has been set as
address error
the system A IP address, system B IP
address, and/or control system IP
address
• Network addresses of the system A IP
address, system B IP address, and
control system IP address are
different.
1200H
Module
• A moderate error has been notified
moderate error
from the intelligent function module
connected.
1210H
• An inter-module synchronous signal
error has been notified from the
intelligent function module connected.
1220H
Another CPU
• A moderate error has been notified
module
from another CPU module.
moderate error
Stop/
Action
continue
Continue
• Check the settings for connection
with the external device.
• Check the operation of the
external device or switching hub.
• Since there may be congestion of
packets on the line, send data
after a certain period of time.
• Check if the Ethernet
communication load is high
because of the Ethernet functions
being executed. Use the Ethernet
functions so that the
communication load is reduced.
• Check if the connection cable is
disconnected.
• Check that there is no connection
failure with the switching hub.
• Execute a PING test. If the test
completes with an error, take an
action to correct the error.
Continue
• Check the settings for connection
with the external device.
• Check the operation of the
external device or switching hub.
• Since there may be congestion of
packets on the line, send data
after a certain period of time.
• Check if the Ethernet
communication load is high
because of the Ethernet functions
being executed. Use the Ethernet
functions so that the
communication load is reduced.
• Check if the connection cable is
disconnected.
• Check that there is no connection
failure with the switching hub.
• Execute a PING test. If the test
completes with an error, take an
action to correct the error.
Continue
• Set different IP addresses for the
system A IP address, system B IP
address, and control system IP
address.
• Set the same network address for
the system A IP address, system
B IP address, and control system
IP address.
Stop/
• Check the detailed information
continue
(system configuration information)
of the error by executing module
diagnostics using the engineering
Continue
tool, identify the error module, and
eliminate the error cause.
Stop/
• Check the detailed information
continue
(system configuration information)
of the error by executing module
diagnostics using the engineering
tool, identify the error module, and
eliminate the error cause.
• Check the mounting status and
reset status of other CPU
modules.
Detailed
Diagnostic
information
timing
Always
Always
Parameter
At power-on, at
information
RESET
System
Always
configuration
information
System
Always
configuration
information
36 ERROR CODES
555
36.4 List of Error Codes