12.5
Communication Status Setting Function at the
Occurrence of a CPU Stop Error
When an error occurs in the CPU module with CC-Link IE TSN Plus modules mounted, whether to stop or continue EtherNet/
IP communications can be set individually for each CC-Link IE TSN Plus module.
Therefore, EtherNet/IP communications can be continued even when the CPU module on which the stop error occurred goes
into the STOP state.
Setting method
Use the buffer memory of the CC-Link IE TSN Plus module for the setting.
Address
Un\G7340104
To stop EtherNet/IP communications when the CPU module changes from RUN to STOP, set 'EtherNet/IP communication
continuation specification request' (Un\G7340104) to a value other than 16 (stop).
To continue EtherNet/IP communications when the CPU module changes from RUN to STOP, set 'EtherNet/IP
communication continuation specification request' (Un\G7340104) to 16 (continue).
When a value other than 16 (stop) is set for 'EtherNet/IP communication continuation specification request'
(Un\G7340104) and the CPU module goes into the STOP state, 'EtherNet/IP communication start request'
(Un\G7340096) becomes 0 (stop request).
12 FUNCTIONS
294

12.5 Communication Status Setting Function at the Occurrence of a CPU Stop Error

Buffer memory
EtherNet/IP communication continuation specification request
Reference
Page 490 EtherNet/IP communication continuation specification
request (Un\G7340104)